5.2. DXR HOME PAGE
1) HOME
The Home page gives a clear overview of the system :
-
current mode of operation
-
direct way to access
2) MAINTENANCE
To get in this section, the following mentions must be used
- Wifi connection
- to select the the Wifi / mode :
• AP mode (Access Point mode). The DXR unit provides its own Wifi network to be accessed with a
smart phone, a laptop, or a touch pad.
• ST mode (Station mode). The DXR unit is connected on the home internet box to access internet
This menu allows :
- To enable or disable the DXR Wi-Fi,
- To change the name of the DXR Wi-Fi (named DXR when the DXR unit is delivered),
- To change the Wi-Fi password (12345678 when the DXR unit is delivered).
- System parameters
This menu allows to access 4 advanced tools.
-
Synoptic. This advanced tool allows to have an overview of the whole system, with all
parameters displayed. It’s also possible, with the set BUS values menu, to take under
control all driven parts (bypass, fan motors, defrosting unit, compensation valve, hub).
-
Synoptic data charts. This tool allows to display the evolution of the device parameters.
-
Configuration wizard. The wizard allows to proceed to the DXR settings. Before starting
to run the DXR, make sure that all the ductwork have been correctly done. The Modbus
communication cable supplies the 2I2O module (if pump or preheater) and the smart
interface (if smart interface), all sensors, the compensation valve and the hub.
-
Reset. This erase all configuration data kept in memory. A new configuration setting by the
use of the wizard is required after a reset.
- Maintenance
-
Filter clogging level
-
Filter status. Reset filters each time filters are replaced
-
Bypass
-
Preheater
- Manufacturer access.
-
K factor is use to adjust airflows. (K=100 for DXR)
-
Preheater set point is the target to drive the preheater. This target is the average value of
the 2 cold T° (1/2 x (outside airflow T° before heat Exc Inside airflow T° after heat
exchanger). This target is 1°C for the DXR when delivered by the factory.
-
Preheater 1200W if 1 preheater (-20°C) / 2400W if 2 preheater (-38°C)
-
Exterior T° set point fixes the minimal exterior T° to proceed free cooling (risk of
condensates in the ductwork if T° is too low) and if supply ductwork is not insulated
(15°C=Factory setting)
-
Interior T° set point to manage the bypass (20°C=Factory setting) in order to start
(automatically) a free cooling or a free warming ventilation when possible.
-
G4 Min Pressure is the pressure drop on the G4 filter @230 m
3
/h when the G4 Filter is the