MAINTENANCE
For every operation of maintenance, even replacement of filters, disconnect the electrical
supply before any operation and ensure that the unit cannot be started accidentally.
Maintenance of ventilation installation helps to avoid:
·microbial contamination of the installations, with consequences on comfort and health (the impact
of such contamination is aggravated in an air supply);
·loss of aeraulic performance through too high pressure drops, increase of fan consumption;
·noise (from a too high pressure, and from high speed rotation of fan due to clogged filters).
8.1. REGULAR MAINTENANCE OF THE INSTALLATION
Frequency
Maintenance
when the alarm indicates it
Replace the filters, then reset filters in the MAINTENANCE MENU.
once a year
Fresh air inlet and exhaust air outlet: check the unobstructed passage of air (no dead leaves, no snow).
Supply and exhaust units: cleaning as recommended by the manufacturer (this part can be done by the occupant).
Evacuation of condensates: check that the system is not obstructed by impurities.
WARNING:
Plan replacement of the condensates evacuation pump according to the life span announced by the supplier. If
using a DXR Unit with a built-in siphon, check that siphons is filled with water. If not, it is necessary to fill the siphon with
water.
Ductwork: check and cleaning if the ductwork is obstructed.
once every 5 years
Exchanger: check the exchanger and clean it with a vacuum cleaner, only if necessary.
Fans:
· check the blades
· check and cleaning if the grilles protecting the fans are obstructed
8.2. POWER SUPPLY AND MOTOR MATERIAL PROTECTIONS
In case of dysfunction of the appliance, these protections will be turned on. It is then necessary to
disconnect the appliance during 30 seconds to restart the DXR Unit.