10.3. TESTS AND MEASUREMENTS:
DEVICE CHECKING
Actions
If pump, test the pump to be sure condensates water is properly rejected.
Disconnect the pipe on the pump (DXR) or take the pump test pipe (DXA), pour some
water and be sure the water evacuation in the waste water network is OK.
Check the pressure in all BXC is OK
Set the machine to mode AUTO by selecting
it on the web interface
Select the pressure of the system according to the dimensioning sheet (60Pa, 80Pa,
100Pa or 120Pa). Wait some minutes until the system finds the balance and measure
the pressure on the BXC grills one by one.
Don’t forget to put the cap back on the pressure measurement hole
BXC1 pressure =
BXC2 pressure =
BXC3 pressurec =
BXC4 pressure =
To be OK, the measured pressure must be the pressure set point +/- 20Pa.
Pa
4
1
2
3
5