Check the device parameters and take a Factory parameters display copy:
In the Factory parameters, check the values (some values may be changed according to
inhabitant expectations):
- K factor: 113 for a DXA, 100 for a DXR (mandatory values),
- Filter clogging threshold: 100% before launching a warming message (may be
changed),
- Preheater set point, average cold T°: +2°C for DXA and +1°C for DXR;
- Exterior temp set point: 15°C (to prevent condensates in the supply network during free
cooling, may be changed (decreased) if pipe insulation is OK),
- Interior temp set point: 20°C (according to the inhabitant expectation and the warming
device set point).
Go to manufacturer access and take a screen shot to put it in the commissioning sheet
In automatic mode, after 2/3 mn (regulation stabilisation), take a synoptic
display copy.
How to load the synoptic page :
Connect to the web interface with a smartphone or PC, and go to the MAINTENANCE
menu,