8 / 56
TF7128_A_NOT_INST_DXR230_EXC_MB
Aereco S.A.
3.
INSTALLATION
3.1. LOCATION OF THE INSTALLATION
The unit must be installed into the heated space, in parts of the dwelling
relatively insensitive to noise, not in the unheated space (attic, etc.).
Upper and lower temperature limits for the main unit are 5°C and 50°C
Ductwork should be installed in the heated space. If not, they must be
insulated with 50 mm minimum of glass wool (or equivalent). The non
compliance with these conditions leads to the degradation of the heat
recovery performance.
Features and uses
DXR Unit and DX Hub
CO
2
sensor
Exhaust compensation valve
Max. altitude of the product installation
2000 m
2000 m
2000 m
Temperature range of the installation place
5°C – 50°C
5°C – 40°C
5°C – 40°C
Humidity range of the installation place
5 % - 95 %
Max. 80 % at 31°C, linear
decrease up to 50 % at 40°C.
5 % - 95 %
3.2. DXR UNIT AND DX HUB
The caps on the DXR Unit must stay during the entire duration of the
work, in order to keep dust and pollution from getting into the boxes.
3.2.1. LOCATION
Before the installation, be sure of the solidity of the ceiling where you plan to install DXR
Unit and DX Hub.
·Weight of DXR Unit = 46 kg
·Weight of DX Hub 6x100 = 11 kg
·Weight of DX Hub 6x75 = 19 kg
·Weight of DX Hub 8x75 = 20 kg
The DXR Unit must be attached so that the gap between the ceiling and the top of the unit
is at least 10 mm, and positioned exactly horizontally (max 1° tolerance).
The non compliance to this requirement may lead to serious problems of
condensate evacuation.
Positionning of the DXR Unit
D > 10 mm
ceiling
ceiling
When mouting the DX Hub, the top must be closed, otherwise the Hub
may wrap.