7 / 36
TF6400_A
Aereco S.A.
wall
(side view)
wall (top view)
3.
INSTALLATION
3.1. LOCATION OF THE INSTALLATION
The unit must be installed into the heated space, in parts of the dwelling relatively
insensitive to noise, not in the unheated space (attic, etc.). Upper and lower
temperature limits for the main unit are 5°C and 50°C
Ductwork should be installed in the heated space. If not, they must be insulated
with 50 mm minimum of glass wool (or equivalent). The non compliance with these
conditions leads to the degradation of the heat recovery performance.
Features and uses
DXA Unit
CO
2
sensor
Exhaust compensation valve
Max. altitude of the product installation
2000 m
2000 m
2000 m
Temperature range of the installation place
5°C – 50°C
5°C – 40°C
5°C – 40°C
Humidity range of the installation place
5 % - 95 %
Max. 80 % at 31°C, linear
decrease up to 50 % at 40°C.
5 % - 95 %
3.2. DXA UNIT
The caps on the DXA Unit must stay during the entire duration of the work, in order to
keep dust and pollution from getting into the boxes.
3.2.1. LOCATION
Before the installation, be sure of the solidity of the wall where you plan to install the DXA
Unit.
·Weight of DXA Unit = 23 kg
The DXA Unit must be positioned exactly vertically (max 1° tolerance).
The non compliance to this requirement may lead to serious problems of condensate
evacuation.
Positionning of the DXA Unit
D = 5 mm
D = 5 mm
Summary of Contents for DXA 230 PREMIUM
Page 33: ...33 36 TF6400_A Aereco S A Notes ...
Page 34: ...34 36 TF6400_A Aereco S A Notes ...