General isolating switch:
The use of a switch - general isolating switch is recommended upward the entire individual proximity
switch. Check that the switch are well opened (no supply) during the installation.
There must be an individual protection for each fan
, using a fuse or a circuit breaker (thermal protection, overload protection
or similar) according to standard EN 60335-1.
Advised fuse: 16A maximum
The supply cable must have 3 conductors
, be between Ø6 mm and Ø12 mm, comply with the installation standards in force
(colour code in particular), have conductors with a cross section of at least 1.5 mm², and be able to withstand the environment
in which it is installed (in particular, be resistant to UV).
Switch - general isolating switch:
A manual circuit breaker must be located on the 230V~ supply, upward the fan(s). It has
to be visible and accessible from each connected fan. It can be shared by several fans or individual depending on the
installation, to allow a quick and easy manual power cut in case of problem or accident.
ST mode:
▪
Case A: 230 V~ electrical box is far from the fans (for example in the stairs)
▪
Case B: 230 V~ electrical box is close to the fans in terrace