POWER CONNECTION
The fans are supplied with 230V~ using a junction box to be installed at the base of the fan. The connection must be done
directly on an electrical box and in no case on a traditional socket.
It is recommanded to use a differential circuit breaker of 300 mA for a group of 10 fans.
The power connection cable of the fan can be identified by the annotation “230 V –
50 Hz” at its edge.
Each wire is marked:
▪
“N” =
neutral
▪
“PE”
= earth protection
▪
“L”
= phase
Edge of the power connection cable
Make the connection in accordance with standard practice via an IP65 junction box installed at the base of the fan.
Recommendation:
Add a grounding strap
and connect it with the M6 screw , on the crimped nut provided for this purpose located on the fan
casing
2
2 Reliée à la terre, cette tresse participe à la réduction des émissions CEM du produit et à limiter le danger dans le cas où le câble menant
au moteur serait coupé (dispositif d'évacuation secondaire).