19/22
TF5774_C
Aereco S.A.
MS MODE
1) Power up the appliance, which then waits for a setpoint command from the management system.
For the rest of the starting up process, please refer to the installation manual of the management modules.
Once the MS mode has been activated, the appliance should start.
The motor technology used may lead to starting errors. If this happens, the appliance fails to start and
begins vibrating slightly. Do not touch anything; the appliance will itself initiate a starting cycle, until it
actually starts.
5.3
INSTALLATION CHECK UP
In order to ensure the proper fonctionning of the installation, do not forget to check the following key points :
Actions
Comments
Check that a 300mA is used for the main differential circuit breaker
□
Measure the power supply (230V) in the derivation box for each
fan
□
Check that all RJ12 cables between modules are pluged according
to the installation and maintenance manual.
□
Check the fixation from devices to plenum (3 Ø8mm
washers)
□
Check the grounding strap connection on the fan body insert
□
Check that there are no foreign bodies inside the product body that
can make noise or prevent the turbine from rotating
□
Check one by one that all devices work properly (turbine rotation)
one it is plugged to 230V (see instructions)
□
Wait 15 minutes (checking time) to ensure there are no error
messages on the modules
□
Check that the numbered modules are connected to the equivalent
fans (Module 1 to fan 1, etc.)
□
Check the group configuration (see module manual)
□