25/36
Aereco S.A.
At the end of the loading process:
Either the appliance has already been set up. In that case, it will be turned into “RUNNING SYSTEM” or
“Defects and failures” mode.
Either the appliance has not been set up already. In that case, it will be turned into “SETTING PROCESS”
mode.
At first use, the appliance will need to be set up. Once it is set up, either in case of power cut, the appliance will
start up to be turned into “RUNNING SYSTEM” mode.
Configuration procedure
This operation is aimed to input the fan groups in the Main module.
All
Fan modules
should be displayed as
"FAULT"
(NOT configured).
If this is not the case, please make a
RESET
.
The
Main module
displays the configuration mode (SETUP mode) as well
as the group being input (here, group n ° 1)
A maximum of 5 fans can be connected to 1 group.