Operation of the management system with wind gauge
A specific wind gauge / anemometer may also be used to supplement or replace the temperature sensor. A
switching wind speed “Vb” can be defined:
If [wind speed < Vb] then operation according to the temperature (if sensor) or maximal speed setting (if
no temperature sensor).
If [wind speed ≥ Vb] then minimum speed (= “natural ventilation” mode).
Operation of the management system with clock
A clock can also be used to supplement or replace the temperature sensor. One or several time period for boost
airflow can then be defined and addressed:
During the “boost airflow” period: Maximum speed of the setting.
Out of “boost airflow” periods: Operation according to the temperature (if sensor) or minimum speed (=
“natural ventilation” mode).