8/36
Aereco S.A.
Technical characteristics of the components
MS management system requires the use of the following components:
Component
Characteristics
Supplier / reference
Quantities
Differential circuit
breaker
C2 type
230 VAC – 2A
Rail DIN
Not specified
1 per Main
module
230 VAC – 5 VDC
Supply
Recommended supply models :
1 per Main
module
A) if from 1 to12 Fan modules:
Linear supply
230 VAC – 5 VDC ; 2,5 W
Rail DIN
A) Comatec brand
ref. TBD2/AR.0050.05/F
B ) if from 13 to 25 Fan modules:
Linear switching power supply
230 VAC – 5 VDC ; 15 W
Rail DIN
Remark : can also be used from one
module, but then will not be optimised for
sizing and cost.
B ) Siemens brand
ref. 6EP1311-1SH03
5V/3A 2
Relay for side
alarm
Plug relay switching 5 VDC relay, simple
contact 10 A+ Rail DIN
Connection to the electric circuit : 250
V
~
max and 10A max.
FINDER – ref :
40.519.005.0300 +
FINDER – ref : 95.05
1 per Main
module
Main module
Power supply in 5VDC
3 wires input for probe
Output « alarm relay » 2 wires: 0-5V (max.
current 200 mA), type « open collector
5VDC ».
Connection through RJ11 wire (supplied) to
Fan modules.
Rail DIN
Aereco – ref. VB21119
1 for up to 25
fans
Fan module
Output 4 wires to send the PWM command
to the fan then to get its speed information.
Connection through RJ11 wire (supplied) to
other Fan modules and to the Main module.
Rail DIN
Aereco – ref. VB21118
1 per fan
2
Summary of Contents for VBP+
Page 11: ...11 36 Aereco S A ...
Page 13: ...13 36 Aereco S A Temperature sensor connection only ...
Page 14: ...14 36 Aereco S A Wind gauge connection only ...
Page 15: ...15 36 Aereco S A Clock connection only ...
Page 16: ...16 36 Aereco S A Temperature sensor wind gauge connection ...
Page 17: ...17 36 Aereco S A Temperature sensor clock connection ...
Page 35: ...35 36 Aereco S A ...