2.2.1 CABLE 

The

 

cable

 

section

 

shown

 

in

 

the

  

table

 

are

 

recommended

 

for

 

maxi

mum

 

lengths

 

of

 

50m.

 

For

 

longer

 

lengths

 

or

 

different

 

cable

 

laying,

 

it

 

is

 

up

 

to

 

the

 

designer

 

to

 

calculate

 

the

 

appropriate

 

line

 

switch,

 

the

 

power

 

supply

 

line

 

as

 

well

 

as

 

the

 

connection

 

to

  

the

  

earth

 

wire

 

and

 

connection

 

cables

 

depending

 

on:

 



length

 



type

 

of

 

cable

 



absorption

 

of

 

the

 

unit

 

and

 

the

 

physical

 

location

 



ambient

 

temperature.

 

ATTENTION: 

Check

 

the

 

tightening

 

of

 

all

 

power

 

wire

 

clamps

 

on

 

commissioning

 

and

 

after

 

30

 

days

 

from

 

start

up.

 

Subsequently,

 

check

 

the

 

tightening

 

of

 

all

 

the

 

power

 

clamps

 

every

 

six

 

months.

 

Loose

 

terminals

 

can

 

cause

 

overheating

 

of

 

the

 

cables

 

and

 

components.

 

2.2.2 CONNECTING POWER SUPPLY 

 



Before

 

connecting

 

the

 

unit

 

to

 

the

 

power

 

supply

 

mains

 

,

 

en

sure

 

that

 

the

 

switch

 

is

 

off

 



Open

 

the

 

front

 

panel

 



Use

 

the

  

holes

 

at

 

the

 

bottom

 

on

 

the

 

framework

 

for

 

the

 

main

 

electric

 

power

 

supply

 

cable

 

and

 

for

 

the

 

cables

 

of

 

the

 

other

 

external

 

connections

 

under

 

the

 

responsibility

 

of

 

the

 

installer.

 



It

 

is

 

forbidden

 

to

 

access

 

with

 

electric

 

cables

 

in

 

positions

 

not

 

specifically

 

envisioned

 

in

 

this

 

manual.

 



Avoid

 

direct

 

contact

 

with

 

not

 

insulated

 

copper

 

piping

 

and

 

with

 

compressor.

 



Identify

  

the

 

clamps

 

for

 

the

 

electric

 

connection,

 

always

 

refer

 

to

 

the

 

electric

 

layout

 

supplied

 

with

 

the

 

unit.

 



For

 

the

 

functional

 

connection

 

of

 

the

 

unit

 

bring

 

a

 

power

 

supply

 

cable

 

to

 

the

 

electric

 

control

 

board

 

inside

 

the

 

unit

 

and

 

connect

 

to

 

the

 

U

N

 

and

 

PE

 

clamps

 

respecting

 

(U)

 

phase,

 

(N)

 

neutral,

 

(PE)

 

earth

 

in

 

case

 

of

 

single

phase

 

power

 

supply

 

(220V

1~60Hz),

 



Re

position

 

the

  

inspection

 

panels

 

 



Ensure

 

that

 

all

 

protections

 

removed

 

for

 

the

 

electric

 

connec

tion

 

have

 

been

 

restored

 

before

 

electrically

 

powering

 

the

 

unit.

 



Position

 

the

 

main

 

system

  

switch

 

(external

 

to

 

the

 

appliance)

 

at

 

“ON”.

 

 

2.2ELECTRICAL CONNECTIONS 

 

The

 

ANK

 

heat

 

pumps

 

are

 

completely

 

wired

 

at

 

the

 

factory

 

and

 

only

 

require

 

connection

 

to

 

the

 

electrical

 

mains,

 

downstream

 

from

 

a

 

unit

 

switch,

 

according

 

to

 

that

 

envisioned

 

by

 

the

 

Standards

 

in

 

force

 

on

 

this

 

subject

 

in

 

the

 

country

 

of

 

installation.

 

 

It

 

s

 

also

 

advised

 

to

 

check

 

the

 

following:

 



The

 

electrical

 

mains

 

features

 

are

 

suitable

 

For

 

the

 

absorption

 

values

 

indicated

 

in

 

the

   

electrical

 

data

 

table

 

in

 

technical

 

manual.

 

Also

 

taking

 

into

 

consideration

 

any

 

other

 

machines

 

operating

 

at

 

the

 

same

 

time.

 



The

 

unit

 

is

 

only

 

powered

 

when

 

installation

 

has

 

been

 

completed

 

(hydraulic

 

and

 

electric).

 



Respect

 

the

 

connection

 

indications

 

of

 

the

 

phase,

 

and

 

ground

 

wires.

 



The

 

power

 

supply

 

line

 

must

 

have

 

a

 

relevant

 

protection

 

mounted

 

upstream

 

against

 

short

 

circuits

 

and

 

dispersions

 

to

 

earth,

 

which

 

isolates

 

the

 

system

 

with

 

Respect

 

to

 

other

 

utilities.

 



The

 

voltage

 

must

 

be

 

within

 

a

 

tolerance

 

of

 

±10%

 

of

 

the

 

nominal

 

power

 

supply

 

voltage

 

of

 

the

 

machine

 

(for

 

unbalanced

 

three

phase

 

unit

 

max

 

3%

 

between

 

the

 

phases).

 

Whenever

 

these

 

parameters

 

are

 

not

 

respected,

 

contact

 

the

 

electric

 

energy

 

public

 

body.

 

For

 

electric

 

connections,

   

use

 

the

 

cables

 

with

 

double

 

isolation

 

according

 

to

 

the

 

Standards

 

in

 

force

 

on

 

this

 

subject

 

in

 

the

 

differentcountries.

 



The

 

use

 

of

 

an

 

omnipolar

 

magnet

 

circuit

 

breaker

 

switch

 

is

 

mandatory,

 

in

 

compliance

 

with

 

the

 

IEC

EN

 

Standards

 

(contact

 

opening

 

at

 

least

 

3

 

mm),

 

with

 

suitable

 

cutoff

 

power

 

and

 

differential

 

protection

 

on

 

the

 

basis

 

of

 

the

 

electric

 

data

 

table

 

shown

 

below,

 

installed

 

as

 

near

 

as

 

possible

 

to

 

the

 

appliance.

 



It

 

is

 

mandatory

 

to

 

make

 

an

 

effective

 

earth

 

connection.

 

The

 

manufacturer

 

cannot

 

be

 

considered

 

responsible

 

for

 

any

 

damage

 

caused

 

by

 

the

 

lack

 

of

 

or

 

ineffective

 

appliance

 

earth

 

connection.For

 

units

 

with

 

three

phase

 

power

 

supply,

 

check

 

the

 

correct

 

connection

 

of

 

the

 

phases.

 

 

Summary of Contents for ANK

Page 1: ... 7 5 7 WATER FLOW RATE ALARM 8 6 MAINTENANCE 8 6 1 HYDRAULIC CIRCUIT 8 6 2 ELECTRICAL CIRCUIT CHECKS 8 6 3 COOLING CIRCUIT CHECKS 8 6 4 MECHANICAL CHECKS 8 6 5 REFRIGERANT LOAD PROCEDURE 8 7 LIST OF CONTROLS 9 8 TROUBLESHOOTING 11 WIRING DIAGRAM 12 WARRANTY 13 ANK INSTALLATION MANUAL NORTH AMERICAN REVISION Table of contents GENERAL WARNING FOR THE INSTALLER The chiller must be installed by a qual...

Page 2: ...ly most desirable Position the heat pump to avoid direct contact with water snow or ice from a roof line overhead The heat pump must be installed on a solid level mounting pad that will not settle or shift Isolate the pad from the building structure to avoid possible transmission of sound or vibration from the heat pump into the conditioned space The heat pump foundation should be raised to a mini...

Page 3: ...gs connected from the disconnect to the heat pump shall be rated for outdoor use Check the heat pump rating plate and follow the appropriate instructions below NOTE All wiring must be suitable for outdoor use Use copper conductors only All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable Electrical wiri...

Page 4: ...sized minimum 1 inch Reducing fitting shall not be used Use care with the water glycol lines during the installation process If pex is used it can be cut by sharp objects Do not remove the caps from the lines or system connection points until connections are ready to be completed 1 Route the supply and return lines from the fittings on the indoor manifold or tank to the fittings on the heat pump R...

Page 5: ...it Position the main system switch external to the appliance at ON 2 2ELECTRICAL CONNECTIONS The ANK heat pumps are completely wired at the factoryand only require connection to the electrical mains downstream from a unit switch according to that envisioned by the Standards in force on this subject in the country of installation It s also advised to check the following The electrical mains feature...

Page 6: ...LED see subsequent pages 4 CONTROLS AND COMMISSIONING 4 1 PREPARATION FOR COMMISSIONING Before starting the unit make sure that 1 All safety conditions have been respected 2 The unit is correctly fixed to the support surface 3 The minimum technical spaces have been respected 4 The hydraulic connections have been made respecting theinlet and outlet 5 The hydraulic plant has been loaded and bled of ...

Page 7: ...he temperature detected by the probe postioned at the outlet of the heat exchanger and in inlet to the chiller is below 4 C 39 F THIS ANTI FREEZE SET TEMPERATURE CAN ONLY BE VARIED BY AN AUTHORISED AFTER SALES CENTRE AND ONLY AFTER HAVING CHECKED THAT THERE IS ANTI FREEZE SOLUTION IN THE WATER SYSTEM The intervention of this alarm determines compressor stop and not pump block which remains active ...

Page 8: ...WHENEVER THIS ALARM INTERVENES WE ADVISE YOU CALL THE NEAR EST AFTER SALES SERVICE IMMEDIATELY 5 7 WATER FLOW RATE ALARM The MODUCONTROL manages a water flow rate alarm controlled by the differential pressure switch installed in series on the machine This type of safety device intervenes after the first 40 seconds of pump function ing if the water flow rate is not sufficient The intervention of th...

Page 9: ...in Fig B To confirm the modification press the key shown in Fig A again 7 LIST OF CONTROLS FOR THE GUIDED PROCEDURE How to modify a parameter in the user menu To enter the USER menu press the key shown in Fig A Once the key has been pressed the password must be inserted for access to the various menus To access the user menu the password is 000 which is the de fault displayed to modify the value o...

Page 10: ...on 5 Envisioned Set the parameter ASA index A INSTALLER MENU with the value 1 4 Is a 3 way diverter valve envisioned in the DHW production circuit Reply Operations to be performed Not envisioned Go to question 5 Envisioned Set the parameter AAS index C INSTALLER menu with the appropriate value in seconds This parameter indicates the stand by tome for inversion of the 3 way diverter valve on the DH...

Page 11: ...rational limits Check Pressure switch dysfunction Replace the component Circuit breaker protection interruption Check power supply voltage Check electric isolation of the windings High discharge pressure High external air temperature High water input temperature Check Insufficient air flow Insufficient water flow Check fan functioning Check pump functioning Fan regulation anomalous functioning Che...

Page 12: ...iler control C F IA AE REF CEI EN 60335 2 40 ATTENTION all others give a reinforced insulation opposed to main power supply line Terminals 6 and 7 provide basic insulation 2RCR 1RCR RCR2 M7S 5 M7S 7 M7S 8 M1 8 M1S 8 M5S1 1 M5S1 2 M7 6 M7 5 M7S 4 M7S 3 RCR1 Contact between 4 5 opened unit off closed unit on Contact between 3 5 opened unit oin heating closed unit on Contact between 10 11 opened unit...

Page 13: ...roper materials or workmanship as determined by MITS the company will at its sole discretion replace the defective part or component Conditions In the event MITS replaces a part or component the repaired or replaced product shall be warranted under the original limited warranty for the remainder of the original warranty period The warranty does not cover any failure of components not supplied by M...

Page 14: ...nding Aermec reserves the right to apply at any time all the modifications deemed necessary for improving the product 1608 Bonhill Road Mississauga ON CA L5T 1C7 Phone 905 564 2221 Canada www aermec ca Toll Free 1 800 567 2221 US www aermec us Toll Free 1 888 567 2227 ...