background image

7

  

5. OPERATION  

5.1. 

SET POINT IN COOLING MODE. PARAMETER 1STF

 

(factory

 

set)=7°C/44.9°F,

 ∆

t=9°C.

  

5.2. 

SET POINT IN HEATING MODE. PARAMETER 3STC

 

(factory

 

set)

 

=

 

45C/113°F,

 ∆

t

 

=

 

9°C.

  

If

 

the

 

unit

 

power

 

supply

 

is

 

restored

 

after

 

a

 

temporary

 

interruption,

 

the

 

set

 

mode

 

will

 

be

 

kept

 

in

 

the

 

memory.

 

5.3. 

COMPRESSOR START-UP DELAY

 

Two

 

functions

 

have

 

been

 

prepared

 

to

 

prevent

 

compressor

 

start

ups

 

that

 

are

 

too

 

close.

  

‐ 

 

Minimum

 

time

  

from

 

last

 

switch

off

 

180

 

seconds.

 

‐ 

 

Minimum

 

time

  

from

 

last

 

switch

on

 

300

 

seconds.

 

5.4. CIRCULATION PUMP 

The

 

circuit

 

board

 

delivers

 

an

 

output

 

for

 

pump

 

management,

 

which

 

starts

 

on

 

commissioning

 

and

 

remains

 

on

 

for

 

at

 

least

 

150

 

seconds

 

and

 

controls

 

the

 

state

 

of

 

the

 

probes.

 

After

 

the

 

first

 

40

 

seconds

 

of

 

pump

 

operation

 

the

 

water

 

flow

 

switch

 

closes

 

and

 

the

 

unit

 

starts,

 

when

 

the

 

water

 

flow

 

rate

 

is

 

in

 

normal

 

working

 

conditions,

 

the

 

water

 

flow

 

rate

 

alarm

 

functions

 

are

 

acti

vated

 

(differential

 

pressure

 

switch

  

or

 

flow

 

meter).

 

When

 

the

 

ma

chine

 

enters

 

stand

by

 

mode,

 

the

 

pump

 

remains

 

on

 

for

 

30

 

sec

 

and

 

controls

 

the

 

flow

 

meter

 

or

 

the

 

pressure

 

switch

 

5.5. 

FAN SPEED CONTROL

 

DCPX ACCESSORY 

COOLING OPERATION AT LOW AMBIENT CONDITIONS 

AND HEATING OPERATION AT HIGH AMBIENT CONDI-

TIONS. 

To

 

allow

 

correct

 

functioning

 

of

 

the

 

unit

 

at

 

different

 

external

 

tem

peratures,

 

the

 

MODUCONTROL

 

by

 

reading

 

the

 

pressure

 

via

 

the

 

pressure

 

probe,

 

controls

 

the

 

rotation

 

speed

 

of

 

the

 

fans,

  

thus

 

allow

ing

 

to

 

increase

 

and/or

 

decrease

 

heat

 

exchange,

 

keeping

 

the

  

con

densation

 

or

  

evaporation

  

pressures

 

more

 

or

 

less

 

constant.

 

The

 

fan

 

functions

 

independently

 

with

 

respect

 

to

 

the

 

compressor.

 

Remem

ber

 

that

 

the

 

DCPX

 

is

 

mandatory

 

for

 

the

 

production

 

of

 

DHW.

 

And

 

cooling

 

below

 

20°C/68°F.

 

5.6. ANTI-FREEZE ALARM 

The

 

anti

freeze

 

alarm

 

is

 

never

 

active

 

if

 

the

 

machine

 

is

 

off

 

or

 

in

 

stand

by

 

mode.

 

In

 

order

 

to

 

prevent

 

breakage

 

of

 

the

 

plate

 

heat

 

exchanger

 

due

 

to

 

freezing

 

of

 

the

 

water

 

it

 

contains,

 

the

 

MODUCONTROL

  

stops

 

the

 

compressor

 

if

 

the

 

temperature

 

detected

 

by

 

the

 

probe

 

postioned

 

at

 

the

 

outlet

 

of

 

the

 

heat

 

exchanger

 

and

 

in

 

inlet

 

to

 

the

 

chiller

 

is

 

below

 

+4°C/39°F.

  

THIS

 

ANTI

FREEZE

 

SET

 

TEMPERATURE

 

CAN

 

ONLY

 

BE

 

VARIED

 

BY

 

AN

 

AUTHORISED

 

AFTER

SALES

 

CENTRE

 

AND

 

ONLY

 

AFTER

 

HAVING

 

CHECKED

 

THAT

 

THERE

 

IS

 

ANTI

FREEZE

 

SOLUTION

 

IN

 

THE

 

WATER

 

SYSTEM.

 

The

 

intervention

 

of

 

this

 

alarm

 

determines

 

compressor

 

stop

 

and

 

not

 

pump

 

block,

 

which

 

remains

 

active

 

along

 

with

 

the

 

switch

on

 

of

 

the

 

resistance

 

if

 

installed.

 

To

 

restore

 

normal

 

functions

 

the

 

tem

‐ 

9.

 

The

 

voltage

 

is

 

within

 

the

 

tolerance

 

of

 

10%

 

of

 

the

 

unit

 

nominal

 

value

 

10.

 

Earthing

 

is

 

correctly

 

made.

 

All

 

electric

 

and

 

hydraulic

 

connections

 

are

 

correctly

 

tightened.

 

4.2. MACHINE COMMISSIONING 

‐ 

Close

 

the

 

electric

 

control

 

board

 

hatch.

 

‐ 

Position

 

the

 

appliance

 

master

 

switch

 

at

 

ON.

 

Make

 

sure

 

that

 

the

 

auxiliary

 

switch

 

contact

 

(IA)

 

 

(see

 

wiring

 

diagram)

 

is

 

open

 

(if

 

used,

 

and

 

the

 

display

 

LED

 

(I)A

 

must

 

be

 

off.

 

Press

 

the

 

ON

 

key

 

for

 

3

 

sec

 

to

 

switch

 

the

 

machine

 

on.

 

4.3. SEASON CHANGEOVER, OPERATION PARAMETERS 

‐ 

For

 

every

 

season

 

change,

 

check

 

that

 

the

 

functioning

 

limits

 

lie

 

within

 

the

 

proper

 

limits.

 

‐ 

Check

 

that

 

the

 

compressor

 

input

 

current

 

is

 

lower

 

than

 

the

 

maximum

 

indicated

 

in

 

the

 

technical

 

data

 

table.

 

‐ 

Make

 

sure

 

that

 

the

 

voltage

 

value

 

lies

 

within

 

the

 

pre

fixed

 

limits

 

and

 

that

 

unbalance

 

between

 

the

 

three

 

phases

 

(three

phase

 

power

 

supply)

 

is

 

not

 

above

 

3%.

 

SEASON CHANGEOVER FROM PANEL ON MACHINE 

Access

 

the

 

USER

 

SET

 

list

 

by

 

touching

 

the

         

insert

 

password

 

key

 

000

 

(already

 

displayed);

 

just

 

confirm

 

by

 

re

pressing

 

the

 

key

       

The

 

parameter

 

affected

 

is

 

the

 

Sta,

 

changing

 

the

 

value

 

0

 

and

 

1

 

will

 

change

 

the

 

operation

 

from

 

cooling

 

to

 

heating

 

accordingly.

 

For

 

further

 

informa

tion

 

refer

 

to

 

the

 

USER

 

MANUAL

 

SEASON CHANGEOVER FROM PR3 

Just

 

act

 

directly

 

on

 

the

 

switch.

 

The

 

machine

 

switches

 

off

 

automatically

and

 

switches

 

back

on

 

with

 

the

 

selected

 

functioning

 

mode.

 

Advance

 

based

 

on

 

the

 

timeframe

 

for

 

the

 

completion

 

of

 

works

  

for

 

the

 

system.

 

Prior

 

to

 

the

 

work

 

to

 

be

 

carried

 

out

 

by

 

the

 

AERMEC

 

service

 

personnel,

 

all

 

other

 

works

 

(electrical

 

and

 

hydraulic

 

hook

ups,

 

priming

 

and

 

bleeding

 

of

 

air

 

from

 

the

 

system)

 

must

 

have

 

been

 

completed.

 

 

Summary of Contents for ANK

Page 1: ... 7 5 7 WATER FLOW RATE ALARM 8 6 MAINTENANCE 8 6 1 HYDRAULIC CIRCUIT 8 6 2 ELECTRICAL CIRCUIT CHECKS 8 6 3 COOLING CIRCUIT CHECKS 8 6 4 MECHANICAL CHECKS 8 6 5 REFRIGERANT LOAD PROCEDURE 8 7 LIST OF CONTROLS 9 8 TROUBLESHOOTING 11 WIRING DIAGRAM 12 WARRANTY 13 ANK INSTALLATION MANUAL NORTH AMERICAN REVISION Table of contents GENERAL WARNING FOR THE INSTALLER The chiller must be installed by a qual...

Page 2: ...ly most desirable Position the heat pump to avoid direct contact with water snow or ice from a roof line overhead The heat pump must be installed on a solid level mounting pad that will not settle or shift Isolate the pad from the building structure to avoid possible transmission of sound or vibration from the heat pump into the conditioned space The heat pump foundation should be raised to a mini...

Page 3: ...gs connected from the disconnect to the heat pump shall be rated for outdoor use Check the heat pump rating plate and follow the appropriate instructions below NOTE All wiring must be suitable for outdoor use Use copper conductors only All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable Electrical wiri...

Page 4: ...sized minimum 1 inch Reducing fitting shall not be used Use care with the water glycol lines during the installation process If pex is used it can be cut by sharp objects Do not remove the caps from the lines or system connection points until connections are ready to be completed 1 Route the supply and return lines from the fittings on the indoor manifold or tank to the fittings on the heat pump R...

Page 5: ...it Position the main system switch external to the appliance at ON 2 2ELECTRICAL CONNECTIONS The ANK heat pumps are completely wired at the factoryand only require connection to the electrical mains downstream from a unit switch according to that envisioned by the Standards in force on this subject in the country of installation It s also advised to check the following The electrical mains feature...

Page 6: ...LED see subsequent pages 4 CONTROLS AND COMMISSIONING 4 1 PREPARATION FOR COMMISSIONING Before starting the unit make sure that 1 All safety conditions have been respected 2 The unit is correctly fixed to the support surface 3 The minimum technical spaces have been respected 4 The hydraulic connections have been made respecting theinlet and outlet 5 The hydraulic plant has been loaded and bled of ...

Page 7: ...he temperature detected by the probe postioned at the outlet of the heat exchanger and in inlet to the chiller is below 4 C 39 F THIS ANTI FREEZE SET TEMPERATURE CAN ONLY BE VARIED BY AN AUTHORISED AFTER SALES CENTRE AND ONLY AFTER HAVING CHECKED THAT THERE IS ANTI FREEZE SOLUTION IN THE WATER SYSTEM The intervention of this alarm determines compressor stop and not pump block which remains active ...

Page 8: ...WHENEVER THIS ALARM INTERVENES WE ADVISE YOU CALL THE NEAR EST AFTER SALES SERVICE IMMEDIATELY 5 7 WATER FLOW RATE ALARM The MODUCONTROL manages a water flow rate alarm controlled by the differential pressure switch installed in series on the machine This type of safety device intervenes after the first 40 seconds of pump function ing if the water flow rate is not sufficient The intervention of th...

Page 9: ...in Fig B To confirm the modification press the key shown in Fig A again 7 LIST OF CONTROLS FOR THE GUIDED PROCEDURE How to modify a parameter in the user menu To enter the USER menu press the key shown in Fig A Once the key has been pressed the password must be inserted for access to the various menus To access the user menu the password is 000 which is the de fault displayed to modify the value o...

Page 10: ...on 5 Envisioned Set the parameter ASA index A INSTALLER MENU with the value 1 4 Is a 3 way diverter valve envisioned in the DHW production circuit Reply Operations to be performed Not envisioned Go to question 5 Envisioned Set the parameter AAS index C INSTALLER menu with the appropriate value in seconds This parameter indicates the stand by tome for inversion of the 3 way diverter valve on the DH...

Page 11: ...rational limits Check Pressure switch dysfunction Replace the component Circuit breaker protection interruption Check power supply voltage Check electric isolation of the windings High discharge pressure High external air temperature High water input temperature Check Insufficient air flow Insufficient water flow Check fan functioning Check pump functioning Fan regulation anomalous functioning Che...

Page 12: ...iler control C F IA AE REF CEI EN 60335 2 40 ATTENTION all others give a reinforced insulation opposed to main power supply line Terminals 6 and 7 provide basic insulation 2RCR 1RCR RCR2 M7S 5 M7S 7 M7S 8 M1 8 M1S 8 M5S1 1 M5S1 2 M7 6 M7 5 M7S 4 M7S 3 RCR1 Contact between 4 5 opened unit off closed unit on Contact between 3 5 opened unit oin heating closed unit on Contact between 10 11 opened unit...

Page 13: ...roper materials or workmanship as determined by MITS the company will at its sole discretion replace the defective part or component Conditions In the event MITS replaces a part or component the repaired or replaced product shall be warranted under the original limited warranty for the remainder of the original warranty period The warranty does not cover any failure of components not supplied by M...

Page 14: ...nding Aermec reserves the right to apply at any time all the modifications deemed necessary for improving the product 1608 Bonhill Road Mississauga ON CA L5T 1C7 Phone 905 564 2221 Canada www aermec ca Toll Free 1 800 567 2221 US www aermec us Toll Free 1 888 567 2227 ...

Reviews: