8. TECHNICAL DATA
TECHNICAL DATA
MODELS
POWER SUPPLY
M.U.
ANL100
ANL150
COOLING MODE
Cooling capacity
Alls
Alls
ton
6.6
8.2
Total input power
H
Alls
kW
8.2
9.5
HP-HA
Alls
kW
9.0
11.0
Water flow rate
Alls
Alls
gpm
15.7
19.5
Evaporator pressure drops
H
-
ft H
2
O
10.04
10.08
Useful head
HP-HA
-
ft H
2
O
45.32
72.25
HEATING MODE
Heating capacity
Alls
Alls
BTU/h
94,755
111,850
Total input power
H
Alls
kW
8.3
9.6
HP-HA
Alls
kW
9.0
11.1
Water flow rate
Alls
Alls
gpm
19.1
22.6
Evaporator pressure drops
H
-
ft H
2
O
14.71
11.87
Useful head
HP-HA
-
ft H
2
O
40.22
70.08
ENERGY INDEX
EER
H
Alls
BTU/W
9.57
10.33
HP-HA
Alls
BTU/W
9.11
9.57
COP
H
Alls
kW/kW
3.35
3.43
HP-HA
Alls
kW/kW
3.18
3.16
IPLV
H
Alls
BTU/W
16.38
17.71
ELECTRICAL DATA
Input current on
COOLING
H
220V 3 ~ 60Hz
A
31.40
36.70
H
460V 3 ~ 60Hz
A
17.10
19.64
HP-HA
220V 3 ~ 60Hz
A
34.26
42.51
HP-HA
460V 3 ~ 60Hz
A
18.66
22.75
Input current on
HEATING
H
220V 3 ~ 60Hz
A
31.59
37.05
H
460V 3 ~ 60Hz
A
17.21
19.83
HP-HA
220V 3 ~ 60Hz
A
34.45
42.86
HP-HA
460V 3 ~ 60Hz
A
18.76
22.93
Peak current (LRA)
H
220V 3 ~ 60Hz
A
168.4
193.2
H
460V 3 ~ 60Hz
A
82.4
95.3
HP-HA
220V 3 ~ 60Hz
A
171.4
198.8
HP-HA
460V 3 ~ 60Hz
A
83.9
98.1
MCA
H
220V 3 ~ 60Hz
A
47.4
55.7
H
460V 3 ~ 60Hz
A
24.3
29.9
HP-HA
220V 3 ~ 60Hz
A
50.4
61.3
HP-HA
460V 3 ~ 60Hz
A
25.8
32.7
MOP
H
220V 3 ~ 60Hz
A
60.0
75.0
H
460V 3 ~ 60Hz
A
30.0
40.0
HP-HA
220V 3 ~ 60Hz
A
60.0
80.0
HP-HA
460V 3 ~ 60Hz
A
30.0
40.0
HEATING CONDITIONS
Inlet water temperature
40°C / 104°F
Outlet water temperature
45°C / 113°F
External air temperature
7°C / 44.6°F b.s
6°C / 42.8°F b.u.
COOLING CONDITIONS
Outlet water temperature
6.7°C / 44.6°F
Flow rate
0.043l/s per kW
External temperature
35°C / 95°F
AHRI conditions: leaving water 6.7°C / 44.6°F
flow rate 0.043 l/s per kW (full load)
Load 100% air 35°C / 95°F
Load 75% air 26.7°C / 80.06°F
Load 50% air 18.3°C / 64.94°F
Load 25% air 12.8°C / 55.04°F
SOUND POWER
Aermec determines sound power values in agree
-
ment with the 9614-2 Standard.
SOUND PRESSURE
Sound pressure measured in free field conditions
with reflective surface (directivity factor Q=2) at
10m/33ft distance from external surface of unit. in
compliance with ISO 3744 regulations.