ANL 

are identified by the following:

  PACKAGING LABEL: that includes the pro-

duct identification data.

  TECHNICAL PLATE: placed on the right strut 

side. (see TAV.1)

NOTE:

If the identification plate, or any other means 
to identify the product, is tampered with, re

-

moved or missing, installation and maintenan

-

ce operations are hampered.

1.  DESCRIPTION AND CHOCE OF UNIT

2.  PRODUCT IDENTIFICATION

TECHNICAL 

PLATE

TAV.1

Chillers and heat pumps for outdoor condensed in 

the air with R410A Series ANL  have been designed 

and manufactured to satisfy heating and cooling 

needs and the production of domestic hot water 

(DHW) in medium to small commercial or residential 

buildings.

These units, have extremely silent functioning and 

are highly efficient and reliable, thanks to the use of 

exchangers with a large exchange surface and low-

noise high-efficiency scroll compressors.

They are available in the following versions:

ANL "°" Standard

ANL "H" Heat pumps

The versions can be in different set-ups at the same 

time in order to satisfy a wide range of plant engine-

ering solutions:

"°" Standard

"P" Pumps

"A" Pump |Storage tank

Summary of Contents for ANL

Page 1: ...and Maintenance Manual TRANSLATION FROM ORIGINAL 21 11 6755517_05 EN DHW PRODUCTION UP TO 122 F EXTERNAL AIR TEMPERATURE UP TO 14 F AVAILABLE VERSION WITH BUILT IN HYDRONIC KIT ANL 60Hz Technical and...

Page 2: ......

Page 3: ...st grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modificat...

Page 4: ......

Page 5: ...BRATION 19 14 SOUND DATA 20 15 GENERAL WARNINGS 21 16 RECEPTION 23 16 1 LIFTING AND HANDLING 23 17 STORAGE 24 18 HYDRAULIC CONNECTIONS 25 19 HYDRAULIC CIRCUITS OF PRINCIPLE 26 19 1 HYDRAULIC CIRCUIT F...

Page 6: ...utdoor condensed in the air with R410A Series ANL have been designed and manufactured to satisfy heating and cooling needs and the production of domestic hot water DHW in medium to small commercial or...

Page 7: ...Model H heat pump 8 VERSION standard P with pump A with storage tank and pump 9 HEAT RECOVERY without heat recovery units 10 COILS in aluminium 11 FIELD OF USE standard 1 12 EVAPORATOR standard PED n...

Page 8: ...transducer HPS High pressure switch LPT Low pressure transducer VIC Cycle reversing valve CN Finned coil CV One way valve F Dehydrator filter AL Liquid storage tank TEV Thermostatic valve BHE Plate e...

Page 9: ...ers and mechanically by anti intrusion metal grids according to the IEC EN 60335 2 40 Standard 5 3 HYDRAULIC CIRCUIT STANDARD COMPONENTS WATER FILTER Equipped with steel filtering mesh prevents the he...

Page 10: ...g times of the compressor in systems with low water content Intelligent defrosting for pressure reduction allows to determine when the coil is effectively defrosted avoiding useless defrosting Set poi...

Page 11: ...NET The device allows the control the management and the remote monitoring of a Chiller with a PC smartphone or tablet using Cloud connection AERNET works as Master while every unit connected is confi...

Page 12: ...k The combined effects of the salt loaded mist and industrial emissions accelerate corrosion Within the manufacturing plants corrosive gas may result from the processing of chemicals or by the typical...

Page 13: ...3 HP HA 220V 3 60Hz A 34 45 42 86 HP HA 460V 3 60Hz A 18 76 22 93 Peak current LRA H 220V 3 60Hz A 168 4 193 2 H 460V 3 60Hz A 82 4 95 3 HP HA 220V 3 60Hz A 171 4 198 8 HP HA 460V 3 60Hz A 83 9 98 1 M...

Page 14: ...fm 8 240 7 946 Input current A 2 2 Input power kW 0 6 0 6 SOUND DATA Sound power dB A 76 0 77 0 Sound pressure 10m 33ft dB A 44 0 45 0 DIMENSION Height in 53 53 Width in 30 30 Depth in 69 69 Weight H...

Page 15: ...15 5 10 14 5 0 32 5 10 50 15 20 68 25 30 86 35 40 104 45 46 C 114 8 F 46 C 114 8 F 50 122 C F 2 35 6 3 4 5 6 41 7 8 9 10 50 11 12 13 14 15 59 16 17 18 19 20 68 C F EXTERNAL AIR TEMPERATURE TEMPERATURE...

Page 16: ...Corrective factor of pressure drop PROPYLENE GLYCOL COOLING MODE CORRECTION FACTOR WITH PROPILENE GLYCOL COOLING MODE Freezing Point C 0 3 43 5 30 7 44 9 98 13 08 16 86 21 47 27 04 33 72 Percent PROP...

Page 17: ...5 80 7 25 8 70 10 15 11 60 0 1000 2000 3000 4000 5000 6000 7000 8000 l h gpm 0 4 9 13 18 22 26 31 35 1 2 1 ANL 100 2 ANL 150 0 2 4 6 8 10 12 14 16 18 20 0 0 0 58 0 29 0 87 1 16 1 45 1 74 2 03 2 32 2 6...

Page 18: ...40 50 Multiplicative coefficients 1 02 1 0 985 0 97 0 95 0 93 0 91 12 2 1 USEFUL HEADS The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Th...

Page 19: ...tem also for glycoled water functioning Values are worked out by multiplying the reference value by the corrective coefficient 13 2 EXPANSION VESSEL CALIBRATION Standard pre load pressure value of exp...

Page 20: ...tor Q 2 at 10mt 33ft distance from external surface of unit in compliance with ISO 3744 regulations KEY Water input temperature 12 C 53 6 F Temperature of produced water 7 C 44 6 F External air tempe...

Page 21: ...check for leaks and make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate v...

Page 22: ...ections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their...

Page 23: ...asporto e movimentazione accluse al presente manuale Controllare che gli accessori necessari all installazione in loco siano stati consegnati e siano funzionanti Se l unit viene fornita precaricata co...

Page 24: ...istance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports re...

Page 25: ...near the suction of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol HYDRAULIC CONNECTIONS The units may be available with or without integrated...

Page 26: ...3 70 300 ppm Chloride ions Cl 50 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressur...

Page 27: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressure switch 3 Water temperature pr...

Page 28: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Water temperature probe 3 Differential pressure swi...

Page 29: ...AVITY A B C D KIT VT Gy Gx ANL100H 650 381 604 32 2 33 3 17 0 17 5 15 P 690 381 640 31 2 32 2 18 0 18 6 15 A 800 381 640 30 1 30 9 19 2 19 8 15 ANL150H 710 382 630 31 4 32 6 17 7 18 3 15 P 756 382 671...

Page 30: ...EN 21 11 6755517_05 30 22 MINIMUM TECHNICAL SPACES A1 C1 B2 C2 B1 ANL 100 150 A1 in 118 2 118 2 B1 in 31 5 31 5 B2 in 43 3 43 3 C1 in 31 5 31 5 C2 in 31 5 31 5...

Page 31: ...ance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the n...

Page 32: ...rator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel mus...

Page 33: ...tions to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position P...

Page 34: ...ust be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropr...

Page 35: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn of...

Page 36: ...cular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simulta...

Page 37: ...proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMM...

Page 38: ...lth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased P...

Page 39: ......

Page 40: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...