33
INSTALLER - Remote control - Climatic curve settings (U2 set as NTC for outdoor air probe)
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the chart that summarises the functioning of the climatic curve applied to the cooling set;
setting at which outdoor air temperature (read by the NTC probe connected at the multi-function
input duly set, as explained in the previous page) the cooling work set remains unchanged and at
which it is increased and by how much
2
Indicates the chart that summarises the functioning of the climatic curve applied to the heating set;
setting at which outdoor air temperature (read by the NTC probe connected at the multi-function
input duly set, as explained in the previous page) the heating work set remains unchanged and at
which it is decreased and by how much
3
It summarises the current system state, indicating the active functioning mode, the temperature
read by the NTC probe connected to the U2 input and the set resulting from the correction accor-
ding to the described curve
ACTIONS
AVAILABLE:
1
A
B
D
2
Go to next page;
Go to alarms menu;
D
E
F
Allows setting at which outdoor air temperature
to use the primary cooling set;
Allows setting at which outdoor air temperature
to raise the primary cooling set;
C
Go back to previous page;
3
G
Allows setting the increase to be applied to the
cooling set for the indicated temperature;
G
E
F
L
H
I
H
I
Allows setting at which outdoor air temperature
to use the primary heating set;
Allows setting at which outdoor air temperature
to lower the primary heating set;
L
Allows setting the decrease to be applied to the
heating set for the indicated temperature;
INSTALLER - Remote control - Climatic curve settings (U2 set as voltage or current value)
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the chart that summarises the functioning of the climatic curve applied to the cooling set;
setting the increase to be applied to the cooling set at maximum of the input signal
2
Indicates the chart that summarises the functioning of the climatic curve applied to the heating set;
setting the decrease to be applied to the heating set at maximum of the input signal
3
It summarises the current system state, indicating the active functioning mode, U2 input value and
the set resulting from the correction according to the described curve
ACTIONS
AVAILABLE:
1
A
B
D
2
Go to next page;
Go to alarms menu;
D
E
F
C
Go back to previous page;
3
Allows setting the increase to be applied to the
cooling set at the maximum of the input signal;
E
F
Allows setting the decrease to be applied to the
heating set at the maximum of the input signal;