22.05 – 4037360_01
43
vironments. To permit the circuit to drain, make sure that the drain
valves have been installed in the lowest points of the circuit and that
they are open.
ANTI-FREEZE PROTECTION
The addition of glycol is the only effective protection against freezing; the glycol/
water solution must be sufficiently concentrated to ensure proper protection and
prevent ice forming at minimum temperature provided for a given installation.
Take the necessary precautions if using non-passivated anti-freeze solu-
tions (monoethylene glycol or monopropylene glycol). Corrosion phenom-
ena may occur with these anti-freeze solutions in contact with oxygen.
However, always refer to the glycol supplier documentation to check its recom-
mended concentration.
IT IS FORBIDDEN! to insert glycol in the hydraulic circuit near the
pump intake:
— A high concentration of glycol and additives that exceeds the permissible limits
could cause the blockage of the pump;
— Do not use the pump as a mixer.