NXP 0500 - 1650 2-PIPE SYSTEM / 4-PIPE SYSTEM

EN

ANOMALY

CAUSE

REMEDY

The unit does not start

• 

No electric voltage

•  Check the presence of voltage

•  Check the safety systems upstream from the appli-

ance

•   Master switch at OFF

• 

 Remote switch at OFF (if present)

•   Control panel at OFF

•   Main switch at OFF

•   Compressor magnet circuit breaker at OFF

• 

Position at ON

• 

 Power supply voltage too low

•   Check power supply line

•   Remote control switch coil broken

•   Circuit board broken

• 

 Peak condenser broken

•   Compressor broken

•   Replace the component

Insufficient yield

• 

No refrigerant

•  Dirty coils

•  Water filter clogged

•  Appliance dimensioning

•  Operation outside of operational limits

•  Check the load and any leaks

•  Clean the coils

•  Clean the filter

•  Check

•  Check the operational limits using the graphics

Noisy compressor

•  Liquid return to the compressor

•  Inadequate fixing

•  Check

•  Inverted phase

•  Invert a phase

Noise and vibrations

•  Contacts between metal bodies

•  Check

•  Weak support

•  Restore

•  Loose screws

•  Tighten the screws

The compressor stops due to intervention 

of the protections

•  Excessive flow pressure

•  Low intake pressure

•  Low power supply voltage

•  Electric connections fastened badly

•  Operation outside of operational limits 

•  Check the operational limits using the graphics

• 

Pressure switch malfunctioning

•  Replace the component

•  Circuit breaker protection intervention

•  Check power supply voltage

•  Check electric isolation of the windings

Compressor high discharge pressure

•  High external water temperature

•  High utility water inlet temperature

•  Check the operational limits using the graphics

•  Insufficient air flow

•  Insufficient water flow

•  Check: 

1.  Fan operation

2.  Cleanliness of the coils

3. 

Pump operation (speed)

4.  Filter cleanliness

•  Fan regulation anomalous operation

•  Check or replace if broken

•   Air in the hydraulic system

•   Bleed the circuit

•  Excessive refrigerant gas load

•  Restore the correct load

Low discharge pressure

•  Low external air temperature

•  Low inlet water temperature

•  Check the operational limits using the graphics, as 

above

•  Humidity in the cooling circuit

•  Empty and restore the gas load

•  Air in the hydraulic system 

•   Bleed the circuit

•  Insufficient gas load

•  Restore the correct load

High intake pressure

•  High external air temperature

•  High utility inlet water temperature

•  Thermostatic expansion valve too open or damaged

•  Check the operational limits using the graphics

•   Adjust or replace if damaged

Low intake pressure

•  Low utility water inlet temperature

•  Low external water inlet temperature

•  Thermostatic expansion valve damaged or blocked

•  Check the operational limits using the graphics

•  Adjust or replace if damaged

•  Insufficient water flow

•   Insufficient air flow

•  Check: 

1.  Fan operation

2.  Cleanliness of the coils

3. 

Pump operation (speed)

4.  Filter cleanliness

TROUBLE SHOOTING

19.  TROUBLE SHOOTING

Summary of Contents for NXP 0500

Page 1: ...21 05 6068956_00 NXP 60Hz 0500 1650 MULTIPURPOSE WATER WATER FOR INDOOR INSTALLATION SCROLL COMPRESSOR PLATE EXCHANGER INSTALLATION MANUAL 60Hz...

Page 2: ......

Page 3: ...k guarantees that our appliances fully comply with the requirements of the European Machinery Directive in terms of safety We constantly monitor the quality level and as a result AERMEC products are s...

Page 4: ...ion on supports 14 9 Electric connections 16 10 Auxiliary connections for standard version 17 11 User interface pgd1 18 12 Displays swichting unit on 19 13 Menu structure and navigation 20 14 Assistan...

Page 5: ...are not respected WARNINGS REGARDING SAFETY AND INSTALLATION STANDARDS 1 Before beginning any operation READ THESE INSTRUCTIONS CAREFULLY AND CARRY OUT THE SAFETY CHECKS TO AVOID ALL RISKS 2 All the s...

Page 6: ...ut sudden movements SELECTION AND PLACE OF INSTALLATION The Units sent from the factory already inspected and only requires electric and hy draulic connections in the place of installation Before begi...

Page 7: ...46 in 2120 mm 1250 mm 2600 mm 49 21 in 102 36 in 795 mm 795 mm 300 mm 300 mm 35 mm 1 38 in 1170 mm 46 06 in 11 81 in 31 30 in 31 30 in 11 81 in 2 95 in 13 98 in 29 72 in 102 36 in 58 66 in DIMENSIONS...

Page 8: ...300 mm 11 81 in 11 81 in 15 94 in 48 11 in 48 11 in 35 mm 1 38 in 1 38 in 1 38 in 35 mm 35 mm 1164 mm 1222 mm 1222 mm 300 mm 405 mm 1202 mm 320 mm 1202 mm 3450 mm 320 mm 405mm 1975 mm 12 60 in 12 60...

Page 9: ...in 2120 mm 83 46 mm 1975 mm 77 76 in 350 mm 1320 mm 1320 mm 13 78 in 350 mm 13 78 in 16 14 in 410 mm 51 97 in 51 97 in 35 mm 1 38 in 35 mm 1 38 in 1320 mm 51 97 in 1320 mm 51 97 in 760 mm 29 92 in 11...

Page 10: ...Victaulic NXP_0500_0750 L 2 1 2 76 1mm 2 1 2 76 1mm 3 88 9mm 3 88 9mm Model Hydraulic Connection Victaulic NXP_0800_1650 Model KEY EV Exchanger side hot cold RC Exchanger side DHW CN Exchanger side g...

Page 11: ...mmended values shown in table in order to limit The hourly number of inversions be tween operating modes Drop in water temperature during win ter defrost cycles WATER FEATURES PH 6 8 Electric conducti...

Page 12: ...able in order to limit The hourly number of inversions be tween operating modes Drop in water temperature during win ter defrost cycles WATER FEATURES PH 6 8 Electric conductivity Less than 200 mV cm...

Page 13: ...ING ATTENTION If the system should stop during the winter period the water present in the exchanger may freeze causing irreparable damage to the exchanger it self There are three solutions possible fo...

Page 14: ...6 0650 without pumps 3 064 4 27 3 60 5 21 23 29 27 0700 without pumps 3 174 7 27 3 61 1 21 24 30 26 0750 without pumps 3 306 9 27 2 65 7 18 27 33 22 AVX365 0800 without pumps 3 505 3 27 1 65 1 18 27 3...

Page 15: ...6 101 7 26 0 73 6 15 24 8 17 27 9 AVX372 1500 max 2 pumps 6 199 7 26 1 73 1 15 24 8 17 27 9 1650 max 2 pumps 6 299 0 26 2 73 2 15 24 8 17 27 9 0500 max 4 pumps 3 461 3 24 8 69 1 21 15 14 21 15 14 AVX...

Page 16: ...ions must be carried out by STAFF IN POSSESSION OF THE NECESSARY QUALIFICATIONS BY LAW suitably trained and informed on the risks related to these operations The features of the electrical lines and o...

Page 17: ...5 4 3 2 1 0 C4 NO8 NO9 NO10 NO11 NO12 RX TX RX TX GND Vout C1 NO1 NO2 NO3 C2 NO4 NO5 NO6 NO7 C3 NC7 G G0 B1 B2 B3 B4 B5 B6 B7 GND Vdc Vdc GND 5 Vref GND Y1 Y2 Y3 Y4 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DIC1 B9...

Page 18: ...ir display The display is made up from a graphical matrix with 132 x 64 pixel in order to signal the type of functioning displaying set parameters and any alarms that have intervened All default se ng...

Page 19: ...i m e s h o w m a s k 20 W a i t p l e a s e 6s A Displays Switching Unit on Unit display Index Display Parameter A Introductory window visible 30 seconds after unit is switched on The seconds remaini...

Page 20: ...Management of the chiller parameters standard energy saving work set point D P1 P1 RECOVERY DHW management parame ters set point consent tem perature time periods etc MAIN SCREEN VISIBLE FOR USER A B...

Page 21: ...rs in cooling mode COLD D 2 PIPES Assistance parameters for the DHW RECOVERY 4 PIPES Assistance parameters in heating mode HOT E NRP FANS Ventilation assistance parameters NXP SOURCE SIDE Pump assista...

Page 22: ...e dure 1 it is possible to scroll the windows that make it up using the arrow keys using the key to pass to the previous parameter and the key to pass to the next parameter previous parameter subseque...

Page 23: ...h the unit Flow switch Pressure switch on closing the cut off valve at the heat exchanger outlet the unit must display the block Finally open the valve and rearm the block MACHINE COMMISSIONING The un...

Page 24: ...ficiency 15 Work pressure 16 Leak test for water tightness control of the cooling circuit 17 Operation of high and low pressure switches 18 Carry out the appropriate checks on the filter dry er to che...

Page 25: ...ce the component Circuit breaker protection intervention Check power supply voltage Check electric isolation of the windings Compressor high discharge pressure High external water temperature High uti...

Page 26: ...current in cooling mode A 42 41 46 51 57 63 84 89 95 108 120 137 154 Total input current in heating mode A 47 48 53 59 67 74 96 102 110 125 139 160 181 Total input current in recovery mode A 47 48 53...

Page 27: ......

Page 28: ...qua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improving the product at any time with an...

Reviews: