background image

6

E

nglish

The regulatory thermostats PXA R are control panels for controlling 
the fan coils equipped with electrical heating elements, to be 
installed on the wall or on the machine.
Each control panel can control a single fan coil.

PXA R controls the working of the fan coil on the basis of the mode 
chosen, the room temperature and the temperature of the water in the 
circuit, to maintain the desired temperature in the room.
The PXA R thermostats can also control fan coils without electrical 
heating elements; in this case it is not necessary to use the selector 
position 

(A), but you must reset the dip switch 10 to disactivate 

the characteristics of the working with heating elements. Before 
proceeding with the installation, check that the settings of the dip 
switches correspond to the type of system being used. 
The layout of the dip switches shown in this manual 
indicates all the possible system combinations.
This manual describes the conditions for the 
installation of fan coils with electric heater inserted 
on 2-pipe systems, with the possibility to connect an 
On - Off valve to intercept the water that feeds the 
battery.

The control panel only consists of mains 
voltage (230V) electrical circuits; all the inputs 
for the probes and controls must therefore be 
correspondingly insulated for this voltage.
The valve servo commands must also be scaled for 
230V.
PXA meets the requirement of the Low Voltage 
directives 73/23 (EN 60730-1, EN 60730-2-9, EN 
60335-1) and electromagnetic compatibility directive 
89/336 (EN 61000-4-1, EN 55011, 55022, 55014).
The panel may only be opened and installed by 
specialised personnel.
Cut off the supply voltage before removing the lid of 
the control panel. Touching live components could 
electrocute you. This is particularly true also for the 
setting of contacts on the Sw1

 

and Sw2 cut outs.

The panel comprises:
– (

A

) on-off selector switch, (manual or automatic) fan speed and 

heating with electric heater;

– (

B

) temperature selector;

– (

C

) blue / red/ fuchsia LEDs, operation mode (Cooling/ Heating/ 

Antifreeze/ Autotest)

– (

D

) yellow led, fan coil operation, Autotest.

+

-

C

A

B

D

V1

 = Minimum speed

 
 

 

V2 

= Medium  speed

 
 

 

V3 

= Top  speed

Heating with heater

OPERATION

The thermostat's job is to keep the temperature set on selector (

B

constant in the room.
The selector switch (

A

) in the 

OFF

 position take two different functions 

that can be programmed during installation:

Frost Protection

, with selector (

A

) in the 

OFF

 position, this prevents 

the temperature, in rooms that are not used for long periods, from 
falling below 7°C, which would make it difficult to reheat them when 
needed. 

If the fan coil is fed with warm water it will start in 

AUTO

 until the 

room temperature is 9°C.

The fan coil, with selector (

A

) in 

position, if not fed with 

warm water, will start up in heating mode with the electric heater at 
medium speed (

V2

) until the room temperature reaches 9°C.

The Frost Protection function must be programmed by the installation 
engineer.

All Off

, with selector (

A

) in the 

OFF

 position, the fan coil is 

completely switched off.

VENTILATION

In the two-pipe system, the thermostat makes it possible to enable 
the heating ventilation only if the temperature of the water exceeds 
35° or 39°C (programmable in the installation phase); in the same 
way, the ventilation in the cooling mode is only enabled if the 
water temperature is less than 17°C or 22°C (programmable during 
installation). 

Ventilation is delayed compared with the start and turn off 
commands.

The functions described on the one hand prevent unwanted cold 
ventilation in winter mode and, on the other, allow all the terminals 
to come on and go off depending on the temperature of the water.
The ventilation mode is set with selector (

A

).

Manual mode

 (selector in position 

V1

V2

V3

) the fan uses the On-

Off cycles at the selected speed.

Automatic mode

 (selector in position 

AUTO

) the fan speed is 

managed by the microcontroller of the PXA R.

The delay between opening or closing of the warm water valve and 
the turning on or off of the fan can last for up to 2’ 40”.

Mode using HEATING ELEMENTS

 (selector in position

)

The electric heater cuts in if the temperature of the water in system is not 
high enough for normal heating operation.
The electrical heating element turns off when the temperature of the 
water in the system reaches the temperature for the normal heating 
operation of the fan coil.

The fan speed is managed by the PXA R microcontroller that turns off (

) speed 

V1 

during normal operation with enabled electric heater 

(i.e. speed 

V2

 will be used as the minimum speed).

When the heater is turned on, the ventilation starts up at speed V1 

that it maintains for forty seconds, then it goes to normal operation 
with the electric heater.

When the electric heater is turned off, the ventilation continues 

at speed 

V2

 for another minute to prevent the electric heater from 

overheating.

AUTOMATIC CHANGEOVER, AIR SIDE

The control makes it possible to automatically set the fan coil 

functioning mode at heating or cooling. 

- In the two-pipe system, no valve systems or those with probe upline 

from the valve, the functioning mode change is determined by the 
temperature of the water circulating in the system.

- In systems with probe upline from the valve, the operational mode 

change is determined by the temperature of the water circulating in 
the system if this has a value above the enabling threshold. 

- In two-pipe systems with probe downline from the valve, and 

in all the systems without water temperature probes, the change 
of operational mode is determined by the difference between the 
temperature measured in the room and the set temperature.

- With the selector (

A

) in position

, the fan coil is only able to 

function in the Heating mode. 

Congratulations on your purchase of the Aermec PXA R control panel with 

electronic thermostat. Made with high-grade materials in close

 compliance with 

safety standards, the “PXA R” is easy to use and will be with you 

for many years to come.

 

Summary of Contents for PXA R

Page 1: ...E POUR VENTILO CONVECTEURS AVEC R SISTANCE LECTRIQUE INSTALLATION MURALE OU SUR L APPAREIL E L E K T R O N I S C H E B E D I E N T A F E L F R GEBL SEKONVEKTOREN MIT ELEKTRISCHEM HEIZREGISTER ZUR WAND...

Page 2: ...e Frost Protection function must be programmed by the installation engineer All Off with selector A in the OFF position the fan coil is completely switched off VENTILATION In the two pipe system the t...

Page 3: ...ng the average and top speeds of the fan The electric heater cuts in if the system s water temperature is not high enough for normal operation Temperature selector B This permits the required temperat...

Page 4: ...2 C Normal set OFF Maximum water temperature 17 C Sw 2 Dip 1 Default OFF Selection of the type of system in which the fan coil is inserted four pipe system set ON two pipe system set OFF Sw 2 Dip 2 De...

Page 5: ...set the switches as indicated in the manual refit the cover being careful of the indicator LEDs the connection cables must be laid inside the device in such a way that the cover fixing screw cannot co...

Page 6: ...elettrico allegato all apparecchio Wiring diagrams may change for updating It is therefore necessary to refer always to the wiring diagram inside the units Les sch mas lectriques peuvent tre modifies...

Page 7: ...Kabelquerschnitt Isolierstoffklasse S c h u t z g r a d d e s Geh uses UMGEBUNGS BEDINGUNGEN Betrieb Temperatur Feuchtigkeit Transporte Temperatur Feuchtigkeit Verschmutzungsgrad Wandmontage Installa...

Page 8: ...A se r serve le droit de modifier tous moments les donn es consid r es n cessaires l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to i...

Reviews: