8
STA_STH_ 4804200 _02
STA/STH
Electronic control | Graphic Display
Sta/Sth are ambient terminals that connected with the control of the ma-
chine, allow the user to adjust the temperature and humidity, and can be
installed fl ush and are compatible with the main wall boxes on the market.
The temperature and humidity adjustment is simple and intuitive thanks to
the front knob; the user can change some environment settings, such as
temperature.
General notes
Avoid installing the boards in environments with the following characteristics:
•
relative humidity greater than that indicated;
•
strong vibrations or shocks;
•
exposure to water jets;
•
exposure to corrosive and pollutant atmospheres (e.g.: sulphur and am-
monia gases, sea mist, smoke) may cause corrosion and/or oxidation;
•
high magnetic and/or radio interference (close to antennas for example);
•
exposure to direct sunlight and atmospheric agents in general;
•
great and rapid fl uctuations in the ambient temperature;
•
environments containing explosive or fl ammable gas mixtures;
•
exposure to dust (formation of corrosive coating with possible oxida-
tion and reduction of insulation).
Installation warnings
These terminals are designed for fl ush mounting with regulatory compli-
ance boxes.
1. Before carrying out any operation on the terminal, remove power
from the device by switching the master switch of the electrical
panel to OFF, then remove the front of the terminal and then the
back to perform the electrical connections;
2. use a shielded three-conductor cable for the serial connection, AWG
20-22. The length of the network should not exceed 500m. For very
large networks add a 120 ohm resistor between RX / TX+ and RX/TX- of
the fi rst and last terminal to avoid possible communication problems.
Assembly
To assemble the rear section a Ø 65 mm by 31 mm deep box is required.
Dimensions of rear parts
Round fl ush box Sta/Sth models
Dimensions
STA/STH
Electronic control
With temperature and humidity probes
STA
Ambient probe with display and adjustment knob
STH
Ambient and humidity probe with display and adjustment knob
TECHNICAL CHARACTERISTICS
Power supply
230 Vac (+10/-15%) 50/60 Hz
Maximum compressor
1 VA
Operating conditions
-10T60 °C, 10…90% R.H. not cond.
Environmental pollution
2
PTI of insulating materials:
from 175 to 249
Software class and structure
A
Protection rating of the casing:
IP20
Category of resistance to heat and fi re:
D
Class C. according to protection
against electric shock
To integrate in class I or II appliances
Surge Immunity:
Category II
Accuracy of the temperature measurement:
Range 0T40 °C: ±1°C; over: ±1.5°C
Accuracy of the humidity measurement
Range 0T60 °C, 20…80% R.H.: +/-5% R.H.
86 mm
86 mm
8
23 mm
28 mm
48 mm
74.00 mm
60.00 mm
74.00 mm
60.00 mm
84.00 mm
59.00 mm
84.00 mm
59.00 mm
T*******C*
Rectangular fl ush box Sta/Sth models
EN
EN
Summary of Contents for STA
Page 2: ......