Open the electric control box:
Remove the metal cover panel by loosening the 4 screws at the front;
2.
Connect the power supply:
the unit must be powered with a voltage of 220-240V~50Hz / 208-230V~60Hz,
connecting the relative input cables to the XT1 control board;
WARNING: the power line must be suitably protected by appropriate circuit brea-
kers;
3.
Connect the WRC1 panel:
To use the unit, connect the WRC1 control panel; this control panel must be con-
nected to terminals H1 & H2 on the XT2 control board.
D1 D2
H1 H2
D1 D2
D1 D2
H1 H2
D1 D2
H1 H2
D1 D2
D1 D2
H1 H2
D1 D2
H1 H2
H1 H2
D1 D2
D1 D2
D1 D2
D1 D2
H1 H2
D1 D2
H1 H2
D1 D2
H1 H2
H1 H2
H1 H2
H1 H2
D1 D2
120Ω
120Ω
120Ω
120Ω
D1 D2
D1 D2
A
B
C
D
Item
Notes
A
Outdoor unit
---
B
TRS1001DX
The terminals are on the XT2 control board of the control box
C
WRC1 Control Panel
WARNING: for more information about length limits and types of installation for the connection cable, refer to the wired
panel manual;
•
The cable must be two-pole twisted and insulated;
•
If the unit is installed in a location with significant electromagnetic interference, it is advisable to use a screened cable
•
Use a two-pole cable having a minimum cross-section of 0.75 ~ 1.25mm
2
;
•
The maximum length of the connection is 250m;
D
Terminating resistor
Supplied as standard with the outdoor unit
TRS1001DX
WRC1(1)
The wired Panel can manage two types of incoming signal from the control device: 100-240V
AC
(50/60Hz) or 5-24V
DC
Depending on the type of signal, the control device must be appropriately connected to the wired panel, as show in the following layouts:
Connecting the wired panel to the external contact with 100-240V
AC
signal
D1 D2
D1 D2
D1 D2
D1 D2
H1 H2
H1 H2
H1 H2
N
L
N
L
H1
H2
H1
H2
100-240V~50/60Hz
Gate control
H1
H2
H1
H2
100-240V~50/60Hz
Gate control
VCC
GND
5-24 V
DC
100-240 V
AC
WRC1
WRC1
WRC1 (1)
WRC1 (2)
Connecting the wired panel to the external contact with 5-24V
DC
signal
D1 D2
D1 D2
D1 D2
D1 D2
H1 H2
H1 H2
H1 H2
N
L
N
L
H1
H2
H1
H2
100-240V~50/60Hz
Gate control
H1
H2
H1
H2
100-240V~50/60Hz
Gate control
VCC
GND
5-24 V
DC
100-240 V
AC
WRC1
WRC1
WRC1 (1)
WRC1 (2)
ELECTRICAL CONNECTIONS TO BE MADE
WARNING:
•
If a serial connection cable with a section of more than 1mm
2
is
used, the total length can be up to 1500m (otherwise, the limit
is 1000m);
•
The cable must be two-pole twisted and insulated;
•
If the unit is installed in a location with significant electromag-
netic interference, it is advisable to use a screened cable
•
The minimum recommended cross-section is 0.75mm
2
NOTE
Refer to the wiring diagram in this manual.