Heat recovery units with refrigeration circuit -
URX_CF
-
6
Selection and installation manual
GB
Description of the components
Panels and structure
:
the structure is made up of 20 mm thick
galvanised self-supporting sandwich panels
with injected polyurethane insulation ( density
of 40 kg/m
3
). The construction of the casing
simplifi es installation and maintenance.
Fans:
double intake centrifugal fans with forward-
curved blades and with directly connected
motor. The 230V - 50 Hz single-phase motor
has one speed. The airfl ow is controlled by
an electronic regulator at phase cut. The two
regulators are set in the factory so as to supply
the nominal performance;
the air volume may
be varied by +/- 15% to the nominal airfl ow,
not to endanger the correct operation of the
unit.
Refrigerating circuit:
this is a highly effi cient and silent heat pump
with scroll compressor, four-way valve for
cycle inversion, evaporating coil, condensing
coil, liquid receiver, liquid separator,
thermostatic valve, liquid indicator, fi lter drier,
high/low pressure switch and the pressure
/ charge connections with access from the
outside of the units.
Condensate drain pan:
made of aluminium alloy, easily detachable.
Evaporating/condensating coil:
with Cu grooved tube and high effi ciency Al fi ns.
Filters:
these are cell type with an corrugated septum
positioned before the recovery unit on airfl ow
supply and return. The standard fi lters are class
G3 type in accordance with classifi cation UNI
EN 779 with weighted effi ciency of 80%. They
are 48 mm thick and are easily withdrawn for
cleaning and replacement.
Dirty fi lters pressure switch:
a differential pressure switch is present, pla-
ced close to the electronic controllers, for the
detection of the choking of the supply fi lter. It
is possible to set the intervention value. Thre
pressure switch includes clean contacts (NA,
NC) to remote the alarm.
Heat recovery unit:
this is static with crossfl ow made of aluminium
sheets. During winter operation, the average
effi ciency is above 50% ensuring fi rst-class
energy recovery from the air expelled from
the room.
Support brackets
:
allow the unit to be rapidly and securely
fi xed to the false ceiling.
Accessibility:
The unit may be inspected from below. The
heat recovery unit, fi lters, condensate drain
pan and fans can be easily removed from
below by removing the lower two panels.
Control system
The unit is equipped with an electrical panel
with power and regulation section (including
the three-way valve for the additional hot
water coil and related servomotor), aimed
at guaranteeing the management of all
refrigerating circuit functions. Also present:
NTC temperature probe on the internal air
recovery, external air temperature probe,
air damper and related servomotor in the
free-cooling version, pressure probe on the
recovery fi lter. A remote control terminal is
also supplied for the automatic management
of the unit, remotable up to 150 meter (cable
not supplied).
The unit is equipped for the management
of a luminous sign (230V) which switches
on in case of generic alarm or unit OFF, in
conformity with the norms in force for rooms
for smokers.
The following operations can be performed
on the microprocessor: switching on and
off of the unit, summer/winter changeover,
setting of set-point parameters, reading of
room temperature.
N.B. For further information refer to
the User manual.
Legenda
1 Compressor
2 Electric panel
3
Centrifugal fan
4
G3 filter
5
Heat recuperator
6
Heat exchanger
7
Condensate drain
8
Electronic regulators
URX_CF
1
2
3
3
4
4
5
6
6
7
8