20
23/05 – 4840212_00
4
PARAMETER LIST
Note: The values shown in the windows are the default values.
Probe parameters
Visualisation
Parameter
Default
rUSr
Water inlet
-
dUSr
Water outlet temperature
-
dSt1
Condensation probe
-
Sprb
External air temperature probe
-
Compressor parameters
Visualisation
Parameter
Default
H1C1
Compressor 1 hour counter
0
H1C2
Compressor 2 hour counter
0
H2C1
Compressor 3 hour counter
0
H2C2
Compressor 4 hour counter
0
HuP1
Evaporator pump hour counter
0
HsP1
Condenser pump hour counter
0
Setting parameters
Visualisation
Parameter
Cooling
Heating
SEtC
Set point summer
11°C
11°C
SEtH
Set point winter
40°C
46°C
U039-U042
Differential
3°C
2°C
U023
Second summer set point from external contact
12°C
12°C
U024
Second winter set point from external contact
40°C
40°C
Attention:
If you set the controller in the “differential” parameter, the following formula must be executed to enter the correct value: Kp= 100 / Differential.