background image

1

1

Set: 21.0°C

TAE1: 4.0°C

Set: 20.0°C

SET1: 0.0°C

TIMED PROGRAM OFF

COMPENSATION SETPOINT OFF

TAE2: 0.2°C

SET2: 0.0°C

OUTDOOR UNIT SETTINGS

OUTDOOR UNIT SETTINGS:

E

E

A

A

B

B

C

C

D

D

Italiano

English

F

ra

n

çais

D

eutsc

h

Es

paño

l

MODIFY OUTDOOR UNIT STATUS

In the window for modifying the outdoor unit (always identified by its indicator 

E

), you can: 

A

Set the heating setpoint:

 press the 

 (increase) and 

 (decrease) keys on 

the same line as the setpoint you want to change.

B

Set the cooling setpoint:

 press the 

 (increase) and 

 (decrease) keys on 

the same line as the setpoint you want to change.

C

Activate or deactivate the timed program on the outdoor unit:

 press the 

key on the same line as the timed program. Each press on this key allows you to select 
one of the following options:

• 

Timed program off:

 no timed programs active on the outdoor units

• 

Timed program on:

 the specific timed program for outdoor units is active (set 

on the relative page of this menu)

• 

Timed program for indoor units:

 the outdoor units use the timed program 

active on the indoor units as their working reference

D

Activate or deactivate compensation on the outdoor unit:

 press the 

 key 

on the same line as the compensation function. Each press on this key allows you to 
select one of the following options:

• 

Compensation setpoint off:

 the setpoint compensation function is not active 

on the outdoor units

• 

Setpoint compensation VS external air:

 the setpoint compensation function 

is active on the basis of the external air temperature

• 

Setpoint compensation VS internal load:

 the setpoint compensation func-

tion is active on the basis of the calculation of the effective load on the indoor 
units (VMF algorithm)

By pressing the 

 key on the lower part of the screen, you can copy the settings 

of the outdoor unit shown in all the other outdoor units of the system (a drop-down 
window will appear, asking for confirmation of the operation).

If the outdoor unit is in alarm mode, the 

 key will turn red and, if pressed, it sends 

a reset command to the specific outdoor unit.

To move on to the next page, press 

 . To return to the previous page, press 

. The 

homepage will be restored automatically if 5 minutes elapse with no interventions.

Setting compensation with external air

In the window for compensation on the outdoor unit selected (always identified by 
its indicator 

E

), you can set: 

A

The minimum outside air temperature for compensation (TAE1):

 to modi-

fy this value, above which the compensation function is activated, press the 
(increase) and 

 (decrease) keys on the same line as the setpoint you want to 

change. 

B

The operating setpoint 1 (SET1):

 to modify this temperature value (that the 

minimum outside air temperature will correspond to), press the 

 (increase) and 

 (decrease) keys on the same line as the setpoint you want to change.

C

The maximum outside air temperature for compensation (TAE2):

 to modi-

fy this value, above which the compensation function is activated, press the 
(increase) and 

 (decrease) keys on the same line as the setpoint you want to 

change. 

D

The operating setpoint 2 (SET2):

 to modify this temperature value (that the 

maximum outside air temperature will correspond to), press the 

 (increase) and 

 (decrease) keys on the same line as the setpoint you want to change.

Compensation on the basis of the outdoor unit is available in both heating and cool-
ing mode. To select the season, press the 

 key.

By pressing the 

 key on the lower part of the screen, you can copy the settings 

of the outdoor unit in all the other outdoor units of the system (a drop-down window 
will appear, asking for confirmation of the operation).

To move on to the next page, press 

 . To return to the previous page, press 

. The 

homepage will be restored automatically if 5 minutes elapse with no interventions.

WARNING: when choosing the compensation curve parameters, air 
temperature 1 (TAE1) must always be lower than outside air tempera-
ture 2 (TAE2). The operating setpoints SET1 and SET2 are not subject 
to any limits.

The compensation curves (one for each season) must be set by describing the 
two points A and B indicated in the diagram below:

[SET °C]

[TAE°C]

TAE1

TAE2

SET1 / SET2

SET1 / SET2

A

B

10

Summary of Contents for VMF E6

Page 1: ...User Manual 6795778_00 VMF E6 ...

Page 2: ...uld not be disposed with other household wastes in the entire EU To prevent any harm to the environment or human health cau sed by incorrect disposal of Waste Electrical and Electronic Equipment WEEE please return the device using suitable collection systems or contacting the retailer where the pro duct was purchased For further information please contact the appropriate local authority The incorr...

Page 3: ......

Page 4: ...omponent To make daily use even easier the information and functions available are grouped into a number of simple user friendly menus where you can find the required function or data To access the menu selection page just press the key in the bottom right hand corner of the main page as shown in the figures alongside STRUCTURE OF THE USER MENUS Each user menu contains one function or more which i...

Page 5: ...tpoint values to be used for heating and cooling The pages of this menu are TIMED PROGRAM SETTING SETPOINT SETTING MZC This menu contains the functions for viewing the current status of the zones where MZC units are installed and for modifying the unit operating parameters The pages of this menu are OUTDOOR UNITS This menu contains the functions for setting the parameters of the outdoor units cont...

Page 6: ...il in automatic mode V1 V3 fancoil active at speed V1 V3 AUX auxiliary command active on the selected fancoil L Type of setpoint active on the selected fancoil LOCAL SET setpoint set by the fancoil thermostat PRG OFF fancoil deactivated via the timed program PRG SET 1 setpoint 1 activated on the basis of the timed program PRG SET 2 setpoint 2 activated on the basis of the timed program M Timed pro...

Page 7: ...ss the key to choose which type of heating to activate in the selected zone this option is only available in the case of a radiant system and with correctly wired VMF REB expansions zone heating with the fancoil only zone heating with the fancoil and radiant floor zone heating with the radiant floor only WARNING in cooling mode the system will only activate the fancoil D The timed program active o...

Page 8: ...pse with no interventions DHW MENU View DHW status In the DHW menu you can view or set the data for DHW production if envis aged and if the DHW management expansion has been correctly installed The information available is as follows A Temperature in the DHW storage tank B DHW setpoint C The timed program active on DHW NO PRG no timed program active on DHW PRG 1 5 timed program 1 5 active on DHW D...

Page 9: ...y pressing the key on the lower part of the screen you can copy the time set tings of the current day in ALL the days of the week a drop down window will appear asking for confirmation of the operation To select a different day of the week press the key on the lower part of the screen To return to the previous page press the key The homepage will be restored au tomatically if 5 minutes elapse with...

Page 10: ...of the current day in ALL the days of the week a drop down window will appear asking for confirmation of the operation Select a different timed program by pressing on the lower part of the screen you can select another timed program Select a different day of the timed program to select a different day of the week press the key on the lower part of the screen To move on to the next page press To re...

Page 11: ...ucting D The timed program active on the selected zone press the increase and decrease keys on the same line as the setpoint you want to change By pressing the key on the lower part of the screen you can copy the settings of the page in ALL the system zones a drop down window will ap pear asking for confirmation of the operation To move on to the next page press To return to the previous page pres...

Page 12: ...ode E Indicates that the outdoor unit is producing domestic hot water F Indicates that the additional heater is active on the outdoor unit G Working power of the selected outdoor unit H Processed water temperature I Setpoint active on the outdoor unit L Temperature of the return water M Outside air temperature The keys along the bottom of the window have various functions Navigate the various outd...

Page 13: ... if pressed it sends a reset command to the specific outdoor unit To move on to the next page press To return to the previous page press The homepage will be restored automatically if 5 minutes elapse with no interventions Setting compensation with external air In the window for compensation on the outdoor unit selected always identified by its indicator E you can set A The minimum outside air tem...

Page 14: ...y program is sub divided into 24 bands one for every hour in which you can define the required outdoor unit status by clicking on the key for the relative hour Each press on this key changes the status of the time band portion as explained below Outdoor units DISABLED By pressing the key on the lower part of the screen you can copy the time set tings of the current day in ALL the days of the week ...

Page 15: ...rmec com Aermec se reserva la facultad de aportar en cualquier momento todas las modificaciones consideradas necesarias para la mejora del producto Aermec se reserva el derecho a efectuar cualquier modificación que estime necesaria para mejorar el producto en cualquier momento con la modificación de los datos técnicos ...

Reviews: