103
7.7.2 Installation of DX coil
RISK OF INJURY! Make sure that the power connection is disconnected, and fan is not moving
before doing any work on the device
-
DX coil inlet - outlet pipes should be insulated.
-
Refer to the electrical diagrams for DX coil signal connections.
After install the accessory, refer to chapter 4.1 for the commissioning.
Assembly area
Observe the following criteria during installation to ensure that the module service is comfortable. (Fig. 95)
A is the minimum distance for servicing the cooling coil.
1.
Apply sealing strip to the surface where the module will be connected with the device (Fig. 96)
Fig. 95
MODEL
A (mm)
EVO-15R
960
EVO-20R
1060
EVO-30R
1170
EVO-50R
1440
EVO-60R
1560
EVO-80R
1810
EVO-95R
1910
EVO-120R
2060
EVO-150R
2310
Fig. 96