31
Alarms triggered by too high or low supply air temperature are activated.
The alarm for the control deviation of the supply air temperature is active.
c. Cascade Room Temperature Control
Note: Only available with KWL-FTF accessory. Connection of the analog output A2 (temperature signal) of the KWL-FTF to the
analogue input AI2 at the controller.
The cascade control of the room and supply air temperature is used to maintain a constant, adjustable room temperature. The
room temperature controller sets the setpoint of the supply air temperature according to the deviation of the ambient
temperature from the room temperature setpoint.
The room temperature SetPoint is in the menu
Temperature
(log in as User or admin).
d. Cascade Extract Air Temperature Control
The cascade control of the extract air and supply air temperature is used to maintain a constant, adjustable room temperature.
The output signal of the extract air temperature control mechanism indicates the setpoint of the supply air.
The set point is in the menu
Temperature
(log in as User or admin).
Control function
↑
Mode
->
Cascade room ctrl
↓
Room temp
↑
Setp: XX.X
°C
↓
If cascade control
↑
Max/min supply setp
Max: XX.X
°C
Min: XX.X
°C
↓
Control function
↑
Mode
->
Cascade extract ctrl
↓
Summary of Contents for EVO-R
Page 1: ...EVO R COMPACT AIR HANDLING UNIT WITH ROTARY HEAT RECOVERY ...
Page 129: ...129 Fig 170 Fig 171 ...
Page 130: ...130 Fig 171 ...
Page 132: ...132 Fig 173 Fig 174 ...
Page 133: ...133 Fig 174 ...
Page 135: ...135 Fig 176 Fig 177 ...
Page 136: ...136 Fig 177 ...
Page 138: ...138 Fig 179 Fig 180 ...
Page 139: ...139 Fig 180 ...
Page 141: ...141 Fig 182 Fig 183 ...
Page 142: ...142 Fig 183 ...
Page 144: ...144 Fig 185 Fig 186 ...
Page 145: ...145 Fig 186 ...
Page 147: ...147 Fig 188 Fig 189 ...
Page 148: ...148 Fig 189 ...
Page 150: ...150 Fig 191 Fig 192 ...
Page 151: ...151 Fig 192 ...
Page 153: ...153 Fig 194 Fig 195 ...
Page 154: ...154 Fig 195 ...
Page 155: ...155 ...