42
In the ventilation on demand menu is selected by “YES” button. With the “UP-DOWN” direction buttons, it is selected as YES
and then press “RIGHT” direction button to select the type of sensor that connected to inputs AI2, AI3, AI4. After the selection of
sensor types, press the “LEFT” direction button to go back Sensor type settings.
In the sensor type menu is entered by “RIGHT” direction button. With the “OK” button Reduced and boost and difference and
stop time can set by the “UP-DOWN” direction buttons and press “OK” to confirm.
•
To perform sensor settings:
o
Reduced: Activation of the ventilation level minimal from this sensor value.
o
Boost: Activation of the ventilation level intensive from this sensor value.
o
Diff: hysteresis
o
Stop time: As soon as the ventilation unit is on the ventilation level for more than time set, sensor-controlled
ventilation is terminated. 0 hours means that the sensor-guided operation is never terminated due to a high
sensor requirement.
Sensor type
AI2: VOC
↓
Sensor type
AI3: CO2
↓
Sensor type
AI4: Humidity
↓
Sensor type
->C02/VOC
Humidity
Reduced:800 ppm
Boost:1000 ppm
Diff:160 ppm
Stop time:2 h
Summary of Contents for EVO-R
Page 1: ...EVO R COMPACT AIR HANDLING UNIT WITH ROTARY HEAT RECOVERY ...
Page 129: ...129 Fig 170 Fig 171 ...
Page 130: ...130 Fig 171 ...
Page 132: ...132 Fig 173 Fig 174 ...
Page 133: ...133 Fig 174 ...
Page 135: ...135 Fig 176 Fig 177 ...
Page 136: ...136 Fig 177 ...
Page 138: ...138 Fig 179 Fig 180 ...
Page 139: ...139 Fig 180 ...
Page 141: ...141 Fig 182 Fig 183 ...
Page 142: ...142 Fig 183 ...
Page 144: ...144 Fig 185 Fig 186 ...
Page 145: ...145 Fig 186 ...
Page 147: ...147 Fig 188 Fig 189 ...
Page 148: ...148 Fig 189 ...
Page 150: ...150 Fig 191 Fig 192 ...
Page 151: ...151 Fig 192 ...
Page 153: ...153 Fig 194 Fig 195 ...
Page 154: ...154 Fig 195 ...
Page 155: ...155 ...