30 - 52

MCH-5-10-14 EVO CNG

MU-BCNG1014-0918

a

ENGLISH

5.3.2

Connecting the compressor to the gas mains

WARNING: Use only a flexible ATEX-certified hose or one 

specifically for use with natural gas; not longer than half a 

meter and at least 1 inch section large.

WARNING: The gas drawn into the compressor from the gas 

mains must not be excessively humid.

The suction pressure must be between 2 and 8 bar.

5.3.3

Electrical connection

The compressor is supplied with an electrical lead but without the power 

lead.

To connect up to the power supply just insert the plug in the mains power 

socket.

Check that the data on the compressor ID plate is compatible with mains 

power supply, especially as regards rated current and voltage.

The mains power system must have an efficient ground (earth); check 

that the earth resistance value complies with the protection / operational 

requirements of the compressor electrical system.

MCH-5-10-14/ET - 16A 3P+E plug not supplied

WARNING: Before inserting the plug, check that the electrical 

system complies with the standards in force in the country 

of installation. A proper earth (ground) system is an essential 

safety requisite.

An efficient compressor ground (earth) system is an essential 

compressor safety requisite.

The mains power connection plug must be type-approved in 

compliance with the relevant standards and have an ON-OFF 

switch (not supplied).
DANGER: Check that the characteristics of the mains power 

are compatible with those of the compressor.

To connect the compressor to the mains gas network:

-  Connect the hose supplied by the authorised installer to the inlet fitting 

(a).

-  Check that there are no kinks or breaks along the pipe. If it is damaged 

replace it.

ESPAÑOL

5.3.2

Conexión del compresor a la red de distribución del gas

ATENCIÓN: Utilizar solamente un tubo flexible certificado 

ATEX o a utilizar para metano; max longitud de 0,5 metros y 

un diámetro de 1“ o mayor.

ATENCIÓN: El gas de aspiración del compresor tomado de la 

red de distribución no debe tener una humedad excesiva.

La presión de succión debe estar entre 2 y 8 bar.

5.3.3

Conexión eléctrica

El compresor se entrega equipado con cable eléctrico, pero sin toma de 

corriente.

Para la conexión eléctrica es suficiente introducir el pasador a la toma de 

alimentación de red.

Compruebe que los datos de la tarjeta del compresor sean compatibles 

con la instalación de red con especial atención a la corriente nominal y a la 

tensión de alimentación.

La instalación de red deberá estar equipada con una puesta a tierra, en 

especial hay que comprobar que el valor de resistencia de tierra respete 

las exigencias de protección y de funcionamiento de la instalación eléctrica 

del compresor.

MCH-5-10-14/ET - Enchufe16A 3P+T no suministrado

ATENCIÓN: Antes de introducir el enchufe, compruebe que la 

instalación se haya realizado siguiendo las normas vigentes 

en el país en el que se instala el compresor.

La instalación eficaz de la puesta a tierra del compresor es una 

característica funda-mental para la seguridad.

La clavija de conexión a la red debe ser de tipo homologado 

según las normativas vigentes en materia y debe contar con 

un interruptor ON-OFF. (no suministrado en dotazione).

PELIGRO: Controle que las características de la red de 

alimentación sean compatibles con las del compresor.

Para conectar el compresor con la red de distribución del gas:

-  Conectar el tubo suministrado por el instalador autorizado a la conexión 

de entrada (a).

-  Compruebe que a lo largo del tubo no haya pliegues ni roturas. Caso que 

la extensión esté rota, sustitúyala.

Summary of Contents for BOOSTER MCH-10/ET CNG

Page 1: ...BOOSTER MCH 10 14 CNG HIGH PRESSURE COMPRESSOR FOR NATURAL GAS CNG NGV COMPRESSORE AD ALTA PRESSIONE PER GAS METANO CNG NGV USE AND MAINTENANCE MANUAL English MANUAL DE USO Y MANTENIMIENTO Espa ol...

Page 2: ......

Page 3: ...URAL GAS CNG NGV This manual is the property of AEROTECNICA COLTRI SpA Reproduction whole or partial is forbidden IMPORTANT BEFORE USING THE COMPRESSOR READ THIS MANUAL CAREFULLY ESPA OL Apreciado cli...

Page 4: ...g the entire use and maintenance manual QUICK GUIDE ESPA OL OPERACIONES PRELIMINARES coloque el compresor en el lugar preelegido v ase cap 5 compruebe el nivel del aceite v ase cap 7 7 conectar el com...

Page 5: ...Wiring diagram 27 ESPA OL NDICE 1 DESCRIPCI N GENERAL 7 1 1 Informaci n preliminar 7 1 2 Requisitos de formaci n de los operadores 7 1 3 Avisos para el uso 7 1 4 Premisa 8 1 5 Garant as 8 1 6 Asistenc...

Page 6: ...ed maintenance registry coupons 49 ESPA OL 5 DESPLAZAMIENTO E INSTALACI N 28 5 1 Embalaje 28 5 2 Desplazamiento 28 5 3 Instalaci n 29 5 3 1 Posicionamiento 29 5 3 2 Conexi n del compresor a la red de...

Page 7: ...mbols and their meaning They highlight essential information ESPA OL AVISO Hace referencia a integraciones o sugerencias para un uso correcto del compresor ATENCI N Hace referencia a situaciones de pe...

Page 8: ...ormas de servicio descritas en el presente manual constituyen parte integrante del suministro del compresor Dichas normas est n destinadas al operador formado expresamente para conducir este tipo de c...

Page 9: ...OL a cargo del cliente en cualquier caso la garant a vence autom ticamente caso que el compresor haya sufrido intervenciones por parte de t cnicos no autorizados por AEROTECNICA COLTRI SpA El compres...

Page 10: ...ere la presi n de ejercicio indicada sobre las mismas Utilice el compresor en ambientes sin polvo y en los que no haya riesgo de explosi n corrosi n o incendio El gas es altamente inflamable por lo ta...

Page 11: ...perfectamente el funcionamiento del aparato y sus mandos y haber le do y comprendido toda la informaci n t cnica contenida en el presente manual Se proh be utilizar el compresor en condiciones o para...

Page 12: ...Tightening torque values 2 1 DESCRIPTION OF THE COMPRESSOR 2 2 IDENTIFICATION THE COMPRESSOR High pressure compressor for natural gas CNG NGV Each compressor has an identification label attached to it...

Page 13: ...stalar usar o llevar a cabo cualquier mantenimiento sobre el compresor Debe guardarse atentamente en un lugar conocido por el usuario del compresor los responsables los encargados del transporte insta...

Page 14: ...and maintenance 3 2 GENERAL PRECAUTIONS ESPA OL La directiva m quinas da las siguientes definiciones ZONAPELIGROSA cualquierzonadentroy ocercadeunam quinaenlaquela presencia de una persona constituya...

Page 15: ...idad Toda operaci n de instalaci n mantenimiento ordinario y extraordinario debe llevarse a cabo con el compresor parado y sin alimentaci n el ctrica Trashaberefectuadolalimpiezadelcompresorcompruebe...

Page 16: ...o sustituci n de partes del compresor no expresamente autorizadas por AEROTECNICA COLTRI El uso de accesorios herramientas materiales de consumo o partes de recambio distintos a las recomendadas por...

Page 17: ...with the cooling fan 8 Danger of direct contact on the part of the operator in the event of disassembly with the compressor at pressure ESPA OL PELIGRO Enalgunaszonasdelcompresorexistenriesgosresidua...

Page 18: ...ertificate maximum working pressure lower than that indicated on compressor 3 3 1 Safety info labels description ESPA OL 3 3 UBICACI N DE LAS PLACAS DE SEGURIDAD No utilice el compresor sin haber le d...

Page 19: ...pecial oils must be used for high pressure compressors To choose the right oil see section 7 7 Oil table ESPA OL a Obligaci n de llevar las gafas de protecci n b Obligaci n de llevar los zapatos de pr...

Page 20: ...l Maximum working pressure Oil drain label Indicates the position of the lubricating oil drain taps ESPA OL Placa de atenci n Se proh be la apertura del panel de mandos por parte de personas no autori...

Page 21: ...a errores de mantenimiento como falta de aceite limpieza insuficiente ineficiencia del circuito del gas comprimido da os de los tubos flexibles apretado de los tubos tornillos etc Realice esmeradament...

Page 22: ...5 4 Keeping the compressor clean 3 5 5 Warning signs ESPA OL El mantenimiento ordinario prescrito en el presente manual debe ser llevado a cabo s lo por personal autorizado y con pr ctica Para el mant...

Page 23: ...ESPA OL 4 DATOS T CNICOS 4 1 1 Monobloque cig e al pistones cilindros 4 1 2 V lvulas 4 1 3 V lvulas de seguridad 4 1 CARACTER STICAS T CNICAS El monobloque est realizado en aleaci n de aluminio las b...

Page 24: ...n 23 Antistatic belt 24 Anti vibration device 25 Pressure switch 26 Gas aspiration connector ESPA OL 4 2 NOMENCLATURA 1 Armaz n 2 Panel de mando 3 Pulsador de encendido 4 Pulsador de paro 5 Contador h...

Page 25: ...x1100 inches 27 6x26 4x43 3 1050mm 41 3 700mm 27 6 670mm 26 4 0 0 1 2 3 4 bar m 3 h 5 6 7 8 9 5 10 15 20 25 MCH 5 MCH 10 MCH 14 ENGLISH 4 3 TECHNICAL CHARACTERISTICS Electric Engine Engine power Volta...

Page 26: ...l cooling pipe 12 Pressure switch 13 Safety valve 14 Pressure gauge 15 Molecular sieve air filter 16 Flex hose ESPA OL 4 4 CIRCUITO DE PRESI N 1 Filtro de aspiraci n 2 Interceptaci n electrov lvula 3...

Page 27: ...MU BCNG1014 0918 MCH 5 10 14 EVO CNG 27 52 ENGLISH 4 5 WIRING DIAGRAM ESPA OL 4 5 ESQUEMA EL CTRICO...

Page 28: ...ith the utmost care when lifting transferring and positioning the compressor ESPA OL El compresor est introducido en una caja de cart n colocada sobre un europallet para que pueda ser desplazada y tra...

Page 29: ...ild up ESPA OL Coloque el compresor en el lugar previsto y compruebe que est nivelado Para las medidas del compresor consulte el p rrafo 4 3 Tabla de las caracter sticas t cnicas Compruebe que en el l...

Page 30: ...it is damaged replace it ESPA OL 5 3 2 Conexi n del compresor a la red de distribuci n del gas ATENCI N Utilizar solamente un tubo flexible certificado ATEX o a utilizar para metano max longitud de 0...

Page 31: ...s on the main power lead ESPA OL El operador debe comprobar que el compresor est equipado con manual de uso y mantenimiento En caso de reventa compresor usado el cliente usuario deber entregar al comp...

Page 32: ...cating oil level check ESPA OL Efect e una inspecci n de los latiguillos de recarga y controle que no presenten cortes orificios quemaduras p rdidas etc Si es necesario c mbielas por latiguillos nuevo...

Page 33: ...ours of the compressor this provides a time reference for scheduled maintenance ESPA OL 6 3 PANEL DE MANDO ATENCI N Se proh be modificar los par metros de presi n sin autorizaci n de AEROTECNICA COLTR...

Page 34: ...a presi n de succi n la presi n de entrada de gas natural es demasiado baja dependiendo de la configuraci n del pres stato de entrada La presi n de la red de distribuci n es demasiado baja P ngase en...

Page 35: ...e emergency pushbutton d To restore normal compressor operation rotate the emergency pushbutton anticlockwise d ESPA OL Puesta en marcha compruebe el voltaje y la puesta a tierra presione el pulsador...

Page 36: ...itting for bus and trucks ESPA OL 6 5 RECARGA AVISO Durante esta operaci n el operador debe mantenerse en el rea de trabajo a Compruebe las condiciones de los dep sitos a llenar Prueba de ensayo del r...

Page 37: ...LLY CLOSED d TO PREVENT THE GAS LEAKAGE DURING DISPENSING ESPA OL Para realizar la recarga con conexi n BC realizar las operaciones descritas a continuaci n 1 Cerrar la llave e haci ndola girar en sen...

Page 38: ...ser efectuadas exclusivamente por el servicio de Asistencia Clientes de AEROTECNICA COLTRI o por personal calificado 7 MANTENIMIENTO PELIGRO No efect e operaciones de mantenimiento si acaba de apagar...

Page 39: ...ge valves Fitting hose leak Safety valve Automatic shutdown check ESPA OL Son aquellas operaciones de reparaci n y o sustituci n de partes mec nicas de uno o varios componentes del compresor que por n...

Page 40: ...hnical assistance 7 5 TROUBLESHOOTING ESPA OL Problema Causa Soluci n El motor el ctrico no arranca Falta una fase Controle los fusibles y lo condensador La velocidad de rotaci n y la capacidad dismin...

Page 41: ...compressor OFF and the power supply lead unplugged from the mains socket ESPA OL La sustituci n del filtro de aspiraci n debe efectuarse cada 4000 horas de uso del compresor o cada 5 a o Para sustitui...

Page 42: ...L Oil table Sump capacity litres Recommended oils ESPA OL Despu s de la primera puesta en servicio es necesario proceder a la sustituci n del aceite lubricante despu s de las primeras 50 horas de uso...

Page 43: ...ivel del aceite El nivel del aceite debe controlarse cada 50 horas de funcionamiento del compresor Controle que el nivel del aceite lubricante c est dentro de los l mites previstos MIN MAX Se recuerda...

Page 44: ...l tensado de las correas La sustituci n de las correas de transmisi n debe efectuarse cada 500 horas de uso del compresor o con una periodicidad anual Comprobaci n del tensado de la correa de transmis...

Page 45: ...re ESPA OL 7 9 SUSTITUCI N DE LOS LATIGUILLOS Para volver a reemplazar los latiguillos de recarga de las botellas siga las indicaciones descritas a continuaci n desconecte los latiguillos de recarga d...

Page 46: ...OD 8 2 STOPPING THE MACHINE FOR A LONG PERIOD ESPA OL Caso que no utilice el compresor gu rdelo en un ambiente seco protegido contra los agentes atmosf ricos y a una temperatura comprendida entre 5 C...

Page 47: ...rtes proceda con la puesta fuera de servicio o el desguace del mismo Dicha operaci n debe efectuarse siguiendo las normativas vigentes 9 DESGUACE PUESTA FUERA DE SERVICIO 9 1 ELIMINACI N DE LOS DESECH...

Page 48: ...STRO DE LOS MANTENIMIENTOS 10 1 SERVICIO DE ASISTENCIA 10 2 INTERVENCIONES DE MANTENIMIENTO PROGRAMADO 10 3 USO DEL COMPRESOR EN CONDICIONES DIF CILES 10 4 EL CUSTOMER CARE CENTRE El cliente tambi n r...

Page 49: ...ANCE SERVICE STAMP TECHNICIAN S SIGNATURE TECHNICIAN S SIGNATURE TECHNICIAN S SIGNATURE TECHNICIAN S SIGNATURE DATE DATE DATE DATE ESPA OL TIPO DE INTERVENCI N Y ANOTACIONES SELLO ASISTENCIA FIRMA T C...

Page 50: ...NCE SERVICE STAMP TECHNICIAN S SIGNATURE TECHNICIAN S SIGNATURE TECHNICIAN S SIGNATURE TECHNICIAN S SIGNATURE DATE DATE DATE DATE ESPA OL TIPO DE INTERVENCI N Y ANOTACIONES SELLO ASISTENCIA FIRMA T CN...

Page 51: ......

Page 52: ...AEROTECNICA COLTRI Spa Via Colli Storici 177 25015 DESENZANO DEL GARDA BS ITALY Tel 39 030 9910301 Fax 39 030 9910283 www coltri com MU BCNG1014 0918...

Reviews: