7.4  Batteries 

 

7.4.1  General 

 
The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the 
number of discharge cycles. 
 
As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is 
performed regularly to ensure failsafe operation (see section 4.6). When the condition of the battery is 
critical, a 'replace battery' alarm will be activated (see 4.4.8). Replace the batteries as soon as 
possible, proceed with section 7.4.2. 

 

 

NOTE 

under certain circumstances a manual battery test can result in a false alarm: please see 
4.6 'quick battery test' 

 

7.4.2  Battery replacement 

 
Please refer to figure 7.4.2. It shows a VH Series 3000VA model. The battery (tray) configuration of 
other models may differ, but the basic principle is the same for all VH Series models. 

 

 

NOTE 

During battery replacement the UPS will not be able to support the load if a mains failure 
occurs! It is recommended to switch off the load before disconnecting the DC connector 
as in step 2. 

 
1. 

Remove the plastic front from 
the UPS cabinet (and/or battery 
cabinet) 

2. 

Disconnect the DC connector 

3. 

Loosen the 4 screws that hold 
the battery tray 

4. 

Slide out the battery tray. Be 
careful: it can be heavy! 

5. 

Insert the new battery tray into 
the UPS, fix it with the 4 
screws. 

6. 

Connect the DC connector. 

7. 

Install the plastic front panel. 

 
 
 
 
 
 
 

If you want to change only the batteries and not  
the full tray with batteries, please contact your dealer. 

 
 

General guidelines: 

 

When replacing the batteries, use only the same type and size 
battery. 

 

Never short the battery terminals. Shorting may cause the battery to 
burn. When working with batteries remove watches, rings or other 
metal objects and only use insulated tools. 

 

Avoid charging in a sealed container.  

fig. 7.4.2 

Summary of Contents for 1000 VA VH Series

Page 1: ...User manual VH Series Uninterruptible Power Supply 700 1000 1500 2000 3000 VA...

Page 2: ...ower of the VH Series UPS the rear panel of the UPS shows the model chapter 9 the ratings 3 2 Installation rules The UPS is intended to be used in normal domestic and office situations Protect the UPS...

Page 3: ...ect the DC connector of the internal batteries 5 Assemble the front panel insert the two metal clamps at the rear of the panel into the holes at the right side of the UPS then click the front panel in...

Page 4: ...max rating 10A To connect the loads to the UPS 700 VA 2 outlets 1000 1500 VA 4 outlets 2000 3000 VA 6 outlets 3a Appliance outlet max rating 16A VH Series 3000 VA only To connect a heavy load to the...

Page 5: ...not exceed the VA output rating of the UPS This way you ensure that the UPS is able to supply the required output and prevent that an overload situation will happen 4 Using the output cords provided...

Page 6: ...power fails and the internal batteries supply the required power until either they are depleted or mains power returns 6 LED alarm blinks in case of an alarm 7 LED bar runtime capacity the remaining a...

Page 7: ...this function is activated the UPS will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will...

Page 8: ...bypass 4 4 3 0 4 0 4 hi o On battery 4 4 4 0 4 0 4 lo Battery low 4 4 5 25 0 4 hi Bypass out of limits 4 4 6 0 4 0 4 lo Overload 4 4 7 0 4 4 hi Replace battery 4 4 8 0 4 0 4 lo General alarm 4 4 9 0 4...

Page 9: ...panel required or if a UPS shutdown command is given by the computer Restart depends on the setting of the auto restart function if set on the UPS will automatically restart when the mains returns if...

Page 10: ...ower failure Allow the UPS to recharge the batteries See also 4 6 4 4 9 General alarm General alarm comprises a group of alarms the buzzer behaviour indicates which alarm is active 1 2 secs General fa...

Page 11: ...the setting of the selected function by pressing switch O The LEDs on the LEDbar runtime capacity shows the setting 4 Store the new settings and leave the setup mode press keypad 1 and keep it presse...

Page 12: ...tery test A deep battery test to be initiated through the UPS software via the USB communication port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep ba...

Page 13: ...al alarm 1 3 Battery low 4 On bypass 5 Remote UPS shutdown RxD 6 GND 1 Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin 1 3 4 Th...

Page 14: ...the same for all VH Series models NOTE During battery replacement the UPS will not be able to support the load if a mains failure occurs It is recommended to switch off the load before disconnecting...

Page 15: ...lso 4 3 3 Line cord not connected Read 3 3 6 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician Tripped Thermal Circuit Breaker See above UPS switch...

Reviews: