background image

 

 

8  -  Troubleshooting 

 
 
Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity 
or load) to determine whether the problem is caused by the unit itself or by its environment. 
Subsequently check the thermal circuit breaker: it may be tripped. If so: reset it (see fig. 3.3.3 a/b) 
and be sure that the UPS is not overloaded. 
The following chart is a simple troubleshooting checklist only. If the suggested solution does not 
succeed, or if the information is insufficient to solve the problem, please contact your dealer or 
consult www.gedigitalenergy.com. 
 

PROBLEM 

POSSIBLE CAUSE 

SOLUTION 

 

 

 

UPS overload 

Reduce load, reset TCB  
(2, fig. 3.3.3 a/b) 

Thermal Circuit Breaker (TCB) 
tripped 

System failure 

Contact your dealer or consult 

UPS will not switch on (without 
using 'battery start') 
and the output has been off for 
a few secs. (see also 4.3.3) 

Line cord not connected 

Read 3.3.6 
Connect line cord 

 

Dead wall socket outlet, or 
mains voltage out of limits 

Contact qualified electrician 

 

Tripped Thermal Circuit 
Breaker 

See above 

UPS switched off automatically 

UPS overtemperature 

Allow UPS to cool down 

 

Mains failure, battery 
discharged 

Wait until mains returns 

 

Programmed shutdown in 
progress 

See 4.4.10 

 

The load is < 5% of the max. 
load and no mains power is 
present. 
(No-load shutdown function is 
active, see 4.3.2) 

Wait until mains returns 

LEDs ‘operation’ and ‘alarm’ 
blink, buzzer sounds 1/2 secs. 
UPS does not start. 

P (phase) and N (neutral) are 
reversed at the UPS input in a 
system with grounded Neutral. 

In a system with grounded 
Neutral: reverse the mains 
plug. 
In other systems: disable the 
indication. See 4.4.12 and 4.5. 

In case of doubt contact a 
qualified electrician.

 

LEDs ‘alarm’ and ‘on battery’ 
blink, buzzer sounds 1/5 secs 

Battery test just after 
installation or mains failure 

Allow the UPS to recharge the 
batteries 

 

Battery test shows weak 
battery 

Read 7.4, have the batteries 
replaced 

 

Summary of Contents for 1000 VA VH Series

Page 1: ...User manual VH Series Uninterruptible Power Supply 700 1000 1500 2000 3000 VA...

Page 2: ...ower of the VH Series UPS the rear panel of the UPS shows the model chapter 9 the ratings 3 2 Installation rules The UPS is intended to be used in normal domestic and office situations Protect the UPS...

Page 3: ...ect the DC connector of the internal batteries 5 Assemble the front panel insert the two metal clamps at the rear of the panel into the holes at the right side of the UPS then click the front panel in...

Page 4: ...max rating 10A To connect the loads to the UPS 700 VA 2 outlets 1000 1500 VA 4 outlets 2000 3000 VA 6 outlets 3a Appliance outlet max rating 16A VH Series 3000 VA only To connect a heavy load to the...

Page 5: ...not exceed the VA output rating of the UPS This way you ensure that the UPS is able to supply the required output and prevent that an overload situation will happen 4 Using the output cords provided...

Page 6: ...power fails and the internal batteries supply the required power until either they are depleted or mains power returns 6 LED alarm blinks in case of an alarm 7 LED bar runtime capacity the remaining a...

Page 7: ...this function is activated the UPS will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will...

Page 8: ...bypass 4 4 3 0 4 0 4 hi o On battery 4 4 4 0 4 0 4 lo Battery low 4 4 5 25 0 4 hi Bypass out of limits 4 4 6 0 4 0 4 lo Overload 4 4 7 0 4 4 hi Replace battery 4 4 8 0 4 0 4 lo General alarm 4 4 9 0 4...

Page 9: ...panel required or if a UPS shutdown command is given by the computer Restart depends on the setting of the auto restart function if set on the UPS will automatically restart when the mains returns if...

Page 10: ...ower failure Allow the UPS to recharge the batteries See also 4 6 4 4 9 General alarm General alarm comprises a group of alarms the buzzer behaviour indicates which alarm is active 1 2 secs General fa...

Page 11: ...the setting of the selected function by pressing switch O The LEDs on the LEDbar runtime capacity shows the setting 4 Store the new settings and leave the setup mode press keypad 1 and keep it presse...

Page 12: ...tery test A deep battery test to be initiated through the UPS software via the USB communication port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep ba...

Page 13: ...al alarm 1 3 Battery low 4 On bypass 5 Remote UPS shutdown RxD 6 GND 1 Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin 1 3 4 Th...

Page 14: ...the same for all VH Series models NOTE During battery replacement the UPS will not be able to support the load if a mains failure occurs It is recommended to switch off the load before disconnecting...

Page 15: ...lso 4 3 3 Line cord not connected Read 3 3 6 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician Tripped Thermal Circuit Breaker See above UPS switch...

Reviews: