User Manual AF-X Fireblocker Nano Series version 3.5
12
b)
Guidelines for the determination of the correct discharge direction
4.
Preferably, generators are mounted to the wall just under the ceiling with the discharge opening directed
downwards.
If a free downward outflow is not possible, the generators can be mounted on the ceiling, also with the
discharge opening directed downwards.
5.
Generators need to be positioned in such a way that all discharged aerosol is dispersed unhampered and
in full in the area to be protected. This also implies that the generators always need to be projected
towards unobstructed space, away from windows, doors, grates, vents, lids, valves, man-holes, transom
windows or other openings. This includes openings that are usually closed or pushed closed with door-
closers or automatically by the FECP before extinguishing starts.
Away from doors:
Away from windows or other potential openings: