In an area with a height of less than 1m, generators should preferably discharge horizontally.
Horizontal discharge in areas lower than 1m:
7.
In an area higher than 1m, generators should preferably discharge downwards at an angle (cf. drawing).
Downward discharge in areas higher than 1m:
8.
In areas up to a hight of 8 m, generators should be placed in the meter of space directly below the
ceiling. For areas higher than 8 m, consult the AF-X Systems experts how to approach a design for a
system for enclosures of such height.
High areas placed within one meter below ceiling: