Parameter
Value
Nozzle capacity
Max. 100 l/h
Return flow
Max. 120 l/h
Separating capacity air/gas,
depending on air content of
fuel
> 4 l/h (de-aeration unit only)
> 6 l/h (as per EN 12514-3)
Mounting position
Float housing vertical to the top
Operating overpressure
Max. 0.7 bar (corresponds to a static
oil column of approx. 8 m)
Suction vacuum
Max. 0.5 bar
Test pressure
6 bar
Filter insert
50 µm, sintered plastic
Materials
De-aerator hood
Transparent plastic
Filter cup
Transparent plastic
Housing
Zinc die cast
Operating temperature range
Ambient/medium
+5 °C to +60 °C
4.1
Approvals, tests and conformities
FloCo-Top-2 is TÜV-tested, report no. S 133 2013 E2.
5
Transport and storage
CAUTION
Damage to the product due to improper transport.
Do not throw or drop the product.
CAUTION
Damage to the product due to improper storage.
Protect the product from shock when storing it.
Store the product in a clean and dry environment.
Do not operate products with visible damages.