background image

2

A 100mm (4in) Type B Gas Vent must be used and fastened
by screw to the draft hood flue collar.

U.S.

The gas vent must be connected to a chimney or
independently and in accordance with Chapter 26, chimney,
Gas Vent and Fireplace Systems of the current issue of
Equipment and Volume of the ASHRAE Handbook. The gas
vent proximity to combustible materials must be installed as
recommended in ANSI/NFPA 211 and according to
manufacturers instructions. Chimneys and vents shall
terminate above roof level and in accordance with the
requirements of the current issue of ANSI/NFPA 211 (see

diagrams) and be at least 1.53m (5ft) above the flue collar
of the draft hood outlet.
Part 7, Venting of Equipment, outlined in the current
National Gas Code ANSI Z223 - latest edition gives detailed
guidelines on all these aspects.

Canada:

The gas vent must be connected to a chimney or
independently and in accordance with the CAN/CGA - B149
installation codes.

The air gap between vent and combustible materials must
be given for the following types of vent:
(i)

Type B Vent - 25mm (1in) minimum.

(ii)

Single wall vent connector - 150mm (6in) minimum.

Listed connectors passing through combustible walls and
partitions must be guarded by a ventilated metal thimble not
less than 200mm (8in) diameter.

Chimneys and vents shall terminate above roof level and in
accordance with the requirement of the current issue of the
CAN/CGA - B149 Installation Code (Code W) (see
diagrams) and be at least 1.53m (5ft) above the flue collar
of the draft outlet.
1.

If suitable lined brick chimney is used it must be 
swept before connection and not less than 150mm 
(6in) internal diameter.

2.

The top of the chimney should be fitted with an 
approved Terminal.

3.

The flue route to the chimney should be as direct as 
possible. Resistance in the form of directional change
should be kept to a minimum. Right angle bends and
horizontal runs should be avoided.

4.

The chimney terminal should terminate at the highest
possible point, preferably in a freely exposed position.
Termination at the roofs eaves is unacceptable.

5.

The Aga Distributor or Local Gas Company should be
advised where any doubt arises as to the suitability of
the flue.

6.

Approved factory made chimneys are acceptable with

VENT CONNECTION

Summary of Contents for GC Open Flue Range

Page 1: ...rial for a minimum thickness of 12mm 1 2in and comply with current Building Regulations and National Fire Laws The wall behind the cooker draft hood and flue connector must have a minimum air gap of 5...

Page 2: ...ng types of vent i Type B Vent 25mm 1in minimum ii Single wall vent connector 150mm 6in minimum Listed connectors passing through combustible walls and partitions must be guarded by a ventilated metal...

Page 3: ...ly from the bottom of an openable window air vent or any other ventilating opening b Within 300mm 12in above adjacent ground level c Within 600mm 24in of any surface facing the terminal d Within 355mm...

Page 4: ...ly piping system at test pressures equal to or less than 1 2 psig 3 5kPa The model and serial numbers for this appliance are found on the name plate These numbers must be used when requesting advice f...

Page 5: ...tablished release the control knob gradually and rotate anti clockwise to its low fire position whereupon the main burner will light Leave in the low fire position for at least 30 minutes NOTE Any att...

Page 6: ...ows Description 1 Pilot Thermocouple 2 Main Burner 3a Pilot Burner Assembly N G 3b Pilot Burner Assembly L P G 4 Combination Gas Valve 5a Pressure Regulator N G 5b Pressure Regulator L P G 6 Combustio...

Page 7: ...7 Fig 12 Pilot Thermocouple DESN 512827...

Page 8: ...he PTFE insulation cable remains intact and strip is firmly connected to the spark electrode Clean any carbon away from the electrode 7 Refit combustion chamber baffle 8 DIRECT VENT MODEL ONLY GC AND...

Reviews: