background image

PRE-INSTALLATION

Before using the stove for the first time all remaining
stickers must be removed, all accessories must be
removed from the ashpan, check if any items have
become dislodged during transport.

CHIMNEY/FLUES

The stove is a radiant room heater and must be con-
nected to a proper type chimney/flue for safe evac-
uation of products of combustion.  The chimney/flue
must have a diameter of 150mm or equivalent cross
sectional area.  Never connect to a smaller size
chimney/flue.  Do not connect to a chimney/flue
serving another appliance.  A minimum chimney/flue
height of 4.5 metres from the flue spigot on the stove
to the top of the chimney/flue is required.  The chim-
ney/flue must be constructed of material capable of
withstanding a soot fire in the chimney/flue which
can lead to temperatures of 1000 degrees.  The
chimney/flue must be constructed with sockets
uppermost so that when condensation occurs within
the pipe, it should flow down the inside of the pipe
that it will transfer to the inner of the next pipe with-
out seeping through the joints.  The chimney/flue
should provide a minimum continuous draught of 12
pascals, if the stove is connected into an existing
chimney where the refractory flue liner is of a diam-
eter in excess of 200mm the chimney should be
relined using a flexible flue liner.  The flexi liner is not
recommended to be connected directly to the appli-
ance, there should be a minimum of 0.6  meters rigid
flue pipe coming off the appliance. The chimney/flue
should be designed to allow for cleaning of the
stove, use pipes with cleaning doors where neces-
sary.   

Avoid the use of 90 degree elbows, use 2 x 45

o

bends instead.  Horizontal runs of flue pipe should
be avoided, where it is unavoidable the maximum
permitted horizontal run is 150mm.  The
chimney/flue must have the necessary clearance
distance from combustible material.  The chimney
termination must be free of any obstructions, see
requirements under Approved Document J, avail-
able to download at www.planningportal.gov.uk

For guidance when installing new chimney systems
or relining existing chimneys please refer to BS EN
15287:

DOWN DRAUGHTS

However well designed constructed and positioned,
the satisfactory performance of the flue can be
adversely affected by down draught caused by near-
by hills, adjacent tall buildings or trees. These can
deflect wind to blow directly down the flue or create 

3

a zone of low pressure over the terminal.  A suitable
anti-down draught terminal or cowl will usually effec-
tively combat direct down blow but no cowl is likely
to prevent down draught due to a low pressure zone.
(See Fig.1)

Direction of wind

Direction of wind

Direction of wind

Pressure zone

Pressure zone

Suction zone

Suction zone

Pressure zone

Suction zone

Fig 1

VENTILATION AND COMBUSTION AIR
REQUIREMENTS

Refer to extract from Building Regulations Part J to
determine size of permanent air vent.

Install where draft stabilizer is fitted:

Permanently open vents as below:
If design air permeability >5.0m

3

/(h.m

2

) then

300mm

2

/kW for first 5kW of appliance rated output

850mm

2

/kW for balance of appliance rated output

If design air permeability <5.0m

3

/(h.m

2

) then

850mm

2

/kW of appliance rated output (4)

Install where no draft stabilizer is fitted:

Permanently open vents as below:
If design air permeability >5.0m

3

/(h.m

2

) then

550mm

2

/kW of appliance rated output above 5kW

If design air permaeability <5.0m

3

/(h.m

2

) then

550mm

2

per kW of appliance rated output (4)

Summary of Contents for Shawbury

Page 1: ...irm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations w...

Page 2: ...rance to Combustibles 5 12 Safe Distance from Chimneys from Flammable materials 5 13 Stove Dimensions 6 14 Technical Data 6 15 Air Controls 7 16 Recommended Fuels 7 17 Refuelling 7 Refuelling onto a l...

Page 3: ...is installed by a Competent Person registered with a Government approved Competent Persons Scheme HETAS Ltd operate such a Scheme and a listing of their Registered Competent Persons can be found on t...

Page 4: ...ee elbows use 2 x 45o bends instead Horizontal runs of flue pipe should be avoided where it is unavoidable the maximum permitted horizontal run is 150mm The chimney flue must have the necessary cleara...

Page 5: ...d other appliances using air in operation at full rate i e extraction fans tumble dryers with all external doors and windows closed If spillage occurs following the above operation an additional air v...

Page 6: ...are must be taken to ensure that there is no risk of ignit ing combustible material an uninsulated flue pipe must be installed at least with a clearance of three times the diameter of the flue pipe i...

Page 7: ...th BS EN 13240 NOTE A suitable chimney minimum profile chimney draft tightness etc is a basic condition for the proper functioning of fireplace stoves See professional advice before installing the sto...

Page 8: ...open position for approximately 3 minutes allowing the new refuel charge to establish combustion before adjusting the air control to the desired setting Refuelling on to a low fire bed If there is in...

Page 9: ...room as the appliance If the alarm sounds unexpectedly follow the instructions given under Warning Note above The most common cause of fume emission is flue way or chimney blockage For your own safet...

Page 10: ...la tively small to permit the refractory to set prop erly and to season the stove 1 Before lighting the stove ensure that any build up in the firebox has been removed and that the ashpan has been empt...

Page 11: ...burning fuel If a build up of creosote occurs on the glass it may be due to draft conditions poor quality fuel or very slow burning for a long time Only clean glass when the stove is thoroughly coole...

Page 12: ...11 EXPLODED VIEW...

Page 13: ...A_0000_081 12 CSN_021103_M6X16 13 031_030_181 14 119A_0000_151 15 119A_0000_131 16 042A_0000_121 17 4901_000_008_23 18 CSN_022301_8X35 19 119A_2000_001 20 544_080_031 21 119A_0000_101 22 001A_0000_271...

Page 14: ...13...

Page 15: ...14...

Page 16: ...AGA Station Road Ketley Telford Shropshire TF1 5AQ UK Rev 001 DP261114 N00642AXX 15...

Reviews: