AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.agfmanufacturing.com
3
Model 5100A/5200A Installation Instructions
Retro-fitting into an Existing System
Isolate branch line or zone where the
1.
COLLECT
an
DRaIn
™
is to be installed.
Relieve air pressure from the branch line.
2.
Remove existing auxiliary drain/condensation collection assembly.
3.
Install the
4.
COLLECT
an
DRaIn
™
by attaching the supply valve (upper) to the
sprinkler system pipe in accordance with NFPA 13 (2013 edition) 8.16.2.5 and
8.16.2.5.3 with regards to low-point drains (auxiliary drains).
Confirm that the supply valve (upper) is in the open position and ready to collect
5.
condensation, the drain valve (lower) is closed, and the plug is tight.
Return system back to normal operating conditions.
6.
Installation into a New System
Install the
1.
COLLECT
an
DRaIn
™
by attaching the supply valve (upper) to the
sprinkler system pipe in accordance with NFPA 13 (2013 edition) 8.16.2.5 and
8.16.2.5.3 with regards to low-point drains (auxiliary drains).
Confirm that the supply valve (upper) is in the open position and ready to collect
2.
condensation, the drain valve (lower) is closed, and the plug is tight.
Activate system for normal operating conditions.
3.
Note:
The presence of even a
small amount
of water in the COLLECT
an
DRaIn
™
Model 5100A will activate the Model 5100ALBV Alarm’s visual and audible
alerts signaling the need for attention. The COLLECT
an
DRaIn
™
must be drained
completely to silence the alarm. Please call 610-240-4900 for instructions on how
to locally silence the audible alert if directly wired to a Fire Control Panel or BMS.
Model 5100A/5200A Operating Instructions
To Collect Condensate per NFPA 25 (2011 edition) A.13.4.4.3.2, 13.4.4.3.2*
Close the drain valve (lower) by making sure the valve handle is perpendicular
1.
to the collection assembly.
Apply Teflon
2.
®
tape to the plug and make sure the plug is tightly threaded into
the bottom of the drain valve.
Slide the Anti-Trip Plate to its lowest position.
3.
Open the supply valve (upper) by making sure the valve handle is in line with
4.
the collection assembly.
If equipped, install the anti-tamper lock.
5.