Agilaire 8872 Manual
Application Notes
Once you have made these settings, you can go into the other three tabs and create the ‘tags’
that you wish to portray to the DCS/SCADA system. These include instantaneous readings and
averages (represented as registers) or digital inputs (represented as coils).
Click in the
*
section at the bottom of the screen to add a new tag:
The scaling factor is only used when the default register format is set to 16-bit integers,
otherwise it is ignored / does not need to be set. The scaling factor is used to convert values
to integers (and the appropriate logic will need to be set on the DCS/SCADA end as well):
Integer Value = Floating Point Value / Scaling Factor
.
Thus, a scaling factor of 0.01 will convert a value of 1.23 into integer ‘123’. Values are rounded.