Chapter 3
45
Configuration
Configuration Methods
Using Telnet Configuration Method (Windows)
To configure the LAN/GPIB Gateway on your network using the Telnet
configuration method from a Windows 95/98/2000/Me/NT client system:
1
Power-on the Gateway by plugging the AC power cord from the
power module into a power outlet (wall outlet).
2
Once the Gateway is powered on, press the
Config Preset
button
on the back panel of the Gateway. This causes the Gateway to
temporarily use its default IP address,
192.0.0.192
. The
LAN
Conn
(LAN Connect) LED on the front panel of the Gateway will
flash slowly, showing that the default IP address is now in use.
3
If not already running, start Windows 95/98/Me or Windows
2000/NT on the client computer system (the Windows PC).
4
From the Windows 95/98/Me task bar at the bottom of the screen,
select
Start
|
Programs
|
MS-DOS Prompt
. The MS-DOS window
opens. Or, from the Windows 2000/NT Program Manager, select
Main
.
Then select
MS-DOS Prompt
. The MS-DOS window opens.
5
At the
>
prompt in the MS-DOS window, type:
route add 192.0.0.192
your_system_name
Enter
This sets up a route table entry on your client system for the
Gateway at its default IP address.
6
At the
>
prompt in the MS-DOS window, type:
telnet 192.0.0.192
Enter
This connects you to the Gateway at its temporary (default) IP
address and the Telnet window opens.
NOTE
If you are unable to make a Telnet connection using the default IP
address (
192.0.0.192
), try pressing the
Config Preset
button again and
then try the
telnet
command (Step 6). If you are still unsuccessful, see
Chapter 5
.
Summary of Contents for E2050
Page 1: ...Agilent E2050 LAN GPIB Gateway Installation and Configuration Guide ...
Page 2: ......
Page 10: ...10 ...
Page 11: ...11 1 Introduction ...
Page 23: ...23 2 Installation ...
Page 32: ...32 Chapter 2 Installation Installing the Hardware Notes ...
Page 33: ...33 3 Configuration ...
Page 63: ...63 4 Administration ...
Page 80: ...80 Chapter 4 Administration Configuring the Gateway Notes ...
Page 81: ...81 5 Troubleshooting ...
Page 99: ...99 A Specifications ...
Page 102: ...102 Specifications Specifications Notes ...
Page 103: ...103 Glossary ...
Page 111: ...Part Number E2050 90003 Printed in U S A E0701 E2050 90003 ...