AGRETO LoadCounter II M
© AGRETO electronics GmbH
page:18
10.3
Too many loads are counted
The parameters may not be set correctly for your application.
If possible, set the pause time higher. However, always orientate yourself
on a short transport process.
Set the number of pulses higher, but they must still be reached safely
with every load.
10.4
Operating hours are not counted completely
The movements or vibrations on the machine are probably relatively low, so that
the necessary intensity for the count is not reached.
Set the parameter SENS down so that the counter triggers even with minor
movements.
To hold longer periods of rest during operation, set the parameter hOLd
upwards.
10.5
Too many operating hours are counted
Perhaps the machine is exposed to light movements at standstill, which are
recorded as operating hours.
Set the parameter SENS upwards so that the counter only triggers for
larger movements
To prevent idle phases from being counted during operation, set the hOLd
parameter down.
10.6
Damage to the device
Contact the manufacturer or your dealer