background image

Ae-man-429-0.0 v1.1 

 

 

 

 

 

 

 

 

USER  MANUAL 

 

www.aguilera.es 

OPERATION 

 

HEATING PERIOD 
 

When the detector is fed, a heating period for the sensor starts, necessary for it to stabilize and carry 
out the correct measure of the METHANE level in the environment. This cycle takes 120 seconds and 
it is shown through the flashing and alternate activation of red light indicators for ALARM and orange 
indicators for FAILURE.   
When this cycle is finished, for correct operation of the detector, only the red indicator for FEEDING 
should be lit continuously. 
 

STANDBY STATE. 
 

This state is shown through fixed lighting of the feeding green indicator. The detector analyses the 
METHANE gas concentration in the environment every 100 milliseconds, its state is updated when 
modifications are produced.     
 

FAILURE STATE. 

If the detector shows any type of anomaly, stopping correct operation, the orange indicator for 
FAILURES  is activated in a continuous way.  
 
 

PRE-ALARM STATE. 
 

When the level of METHANE gas concentration is over 10% L.I.E., the detector activates (1 time per 
second) the acoustic alarm and the red indicator for ALARM in an intermittent way.  
 

ALARM STATE. 
 

If the pre-alarm state is confirmed for 10 consecutive seconds, the detector goes to alarm state, 
activating the acoustic alarm and the red indicator for ALARM in a continuous way. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
If required, the acoustic alarm can be silenced by pressing the SW1 pushbutton placed inside the 
detector.  
 

OPERATION RELAY ACTIVATION 

Operation relay activation is produced 8 seconds after confirming the alarm state.  
 
 

 
DETECTOR REPLACEMENT. 
 

 

In case of ALARM. 
 

1.  Extinguish the flames.  
2.  Cut off the gas supply from the gas main control.  
3.  Do not turn the lights on or off, or any electric unit. 

 
Open the windows for ventilation. When the alarm stops, the reason for the alarm to be activated is 
to be determined and measures are to be taken. If the alarm continues on, and the is no apparent 
cause for the leak and/or it can not be repaired, vacate the place and IMMEDIATELY NOTIFY the 
emergency service from a safe place. Gas detectors are accuracy instruments.  
 

Summary of Contents for AE09/GM-12

Page 1: ...tly on a cutting device and or other auxiliary devices It is provided with Green light indicator for feeding and operation detector Alarm red light indicator Failure orange light indicator Acoustic in...

Page 2: ...emperature may decrease below 10 C or over 40 C In places where dust and dirt may block the sensor In a wet or humid place WARNINGS Installation and dismantling of these devices is to be made by autho...

Page 3: ...to be feed at 12V DC for proper performance Such tension from a power supply is to be directly connected to CL2 terminal AE09 GM 24 Model AE09 GM 24 needs to be feed at 24V DC for proper performance...

Page 4: ...0 v1 1 USER MANUAL www aguilera es Feeding examples for normally fed electrovalves Electrovalves are usually open when being fed When cutting off the power supply blocks the gas flow and manual reset...

Page 5: ...ARM STATE When the level of METHANE gas concentration is over 10 L I E the detector activates 1 time per second the acoustic alarm and the red indicator for ALARM in an intermittent way ALARM STATE If...

Page 6: ...ny case it has been calibrated below the level of gas explosion The detector should be installed between 1 and 4 metres from gas appliances The detector should not be installed in a closed place for e...

Page 7: ...coustic indication intermittent activation Alarm state indicator Red and acoustic indication fixed activation Acoustic alarm piezoelectric buzzer 3300Hz 85 dB Alarm level 10 L I E METHANE gas CH4 Alar...

Page 8: ...08 04 Fax 93 381 07 58 EAST OFFICE Tel 628 92 70 56 Fax 91 754 50 98 NORTHWEST OFFICE C Jos Luis Bugallal Marchesi 9 15008 A Coru a Tel 98 114 02 42 Fax 98 114 24 62 SOUTH OFFICE Edificio METROPOL 3...

Reviews: