46
Installing a Remote Control
Device
Automation Controller
Heater 2-Wire Controllers (Heat Only)
1. Install wires from the automation controller for
“Heat” on the terminal strip inside the HPPH on the
terminals: # 44 (Com) & # 46 (Spa).
2. Press and hold the UP and DOWN buttons for 3 +
seconds to enter the Remote Mode.
3. When in the Remote Mode, the maximum setpoint
is the SPA MAX TEMP (104F Default).
4. Press and hold the UP and DOWN buttons for 3 +
seconds to exit the Remote Mode.
5. The digital board will default to the OFF mode
allowing the user to select the appropriate mode
under local control.
3-Wire Controllers
1. Install wires from the automation controller for
“Heat” on the terminal strip inside the HPPH on the
terminals: # 44(Com), # 45 (Pool) & # 46 (Spa).
2. Set the Remote Pool to “Heat” or “Auto” in the
INSTALLER menu. Selecting “Heat” will allow
remote heating of the pool. Selecting “Auto” will
Fig. 14: Heater Wiring Block
allow heating & cooling of the pool around the
SETPOINT value established in the USER mode
(HEAT/COOL models only). The control will use
this value as the Heating setpoint and the Cooling
Setpoint will be the SETPOINT + COOLING
DEADBAND (established in the INSTALLER
menu).
3. Press and hold the UP and DOWN buttons for 3 +
seconds to enter the Remote Mode.
4. When in the Remote Mode, the maximum setpoint
is the SPA MAX TEMP (Spa) & POOL MAX TEMP
(Pool).
5. Press and hold the UP and DOWN buttons for 3 +
seconds to exit the Remote Mode.
6. The digital board will default to the OFF mode
allowing the user to select the appropriate mode
under local control.
2-Wire Controllers For “Chill” Mode – Heat
/Cool Models Only
1. Install wires from the automation controller for the
“CHILL” mode on the terminal strip inside the
HPPH on the terminals: # 44 (Com) & # 45 (Pool).
2. Set the Remote Pool in the INSTALLER menu to
“Cool”.
3. Set the desired COOL SETPT setpoint tempera-
ture in the POOL mode.
4. Press and hold the UP and DOWN buttons for 3 +
seconds to enter the Remote Mode.
5. When in the Remote Mode, the operating setpoint
is the COOL SETPT value established in the
USER menu.
6. Press and hold the UP and DOWN buttons for 3 +
seconds to exit the Remote Mode.
7. The digital board will default to the OFF mode
allowing the user to select the appropriate mode
under local control.
NOTE:
When the automation controller has a HEAT
command the HPPH is in the SPA mode. When the
automation controller does not have a HEAT com-
mand the HPPH is in the OFF mode.
NOTE:
Heating of the water will automatically occur
if the temperature drops to a value equal to the
COOLING DEADBAND degrees below the cooling
setpoint.