background image

31

RC SERIES INSTALLATION MANUAL

Control and Safety Feature Details

 

Emergency Shutdown

The emergency shutdown mode can be activated by a command 
from a facility management system or a closed contact on BI-2. 
The default state for the emergency shutdown data point is off. 
When the emergency shutdown mode is activated, all outputs will 
be turned off immediately and will remain off until the emergency 
shutdown mode is de-activated. The first time the compressor 
starts after the emergency shutdown mode has been de-activated, 
there will be a random start delay present.

Lockout Mode

Lockout mode can be activated by any of the following fault signals: 
refrigerant system high pressure, refrigerant system low pressure, 
water coil low temperature (freeze sensing), and condensate 
overflow. When any valid fault signal remains continuously active for 
the length of its recognition delay, the controller will go into fault retry 
mode, which will turn off the compressor. After the Compressor short 
cycle delay, the compressor will attempt to operate once again. If 
three consecutive faults occur in 60 minutes during a single heating 
or cooling demand, the unit will go into lockout mode, turning off the 
compressor, enabling the alarm output, and setting the fan back 
to low speed operation until the controller is reset. If the control 
faults due to the low pressure input (BI-3) being open during the 
pre-compressor startup check, the control will go into lockout mode 
immediately, disabling the compressor from starting and enabling the 
alarm output (BO-6). The lockout condition can be reset by powering 
down the controller, by a command from the BAS, or by the holding 
the ESC and Return keys on the MUI for 5 seconds.

Water Coil Low Temp (Freeze Sensing) Limit (AI-5)

The water coil low temperature (freeze sensing) limit sensor will 
monitor the liquid refrigerant temperature entering the water coil 
in the heating mode. If the temperature drops below the water coil 
low temperature (freeze sensing) limit trip point for the recognition 
delay period, the condition will be recognized as a fault. The 
water coil low temperature (freeze sensing) limit trip point will 
be factory set for 30°F and will be field selectable for 15°F by 
removing a jumper wire on BI-5. The water coil low temperature 
(freeze sensing) limit fault condition will be bypassed 2 minutes 
at normal compressor startup, to allow the refrigeration circuit to 
stabilize. If the water coil low temperature (freeze sensing) limit 
sensor becomes unreliable at any time compressor operation will 
immediately be suspended until the problem is corrected. This 
should be displayed as an alarm on the BAS and the MUI. This 
alarm will be reported a “Water Low Temp Limit” fault.

High Pressure (BI-11)

The high-pressure switch shall be a normally closed (NC) switch 
that monitors the systems refrigerant pressure. If the input senses 
the high-pressure switch is open it must disable the compressor 
output immediately and count the fault. The compressor minimum 
on time does not apply if the high-pressure switch opens. The 
compressor will not restart until the compressor short cycle time 
delay has been satisfied.

Low Pressure (BI-3)

The low-pressure switch shall be a normally closed (NC) switch 
that monitors the systems refrigerant pressure. The input shall be 
checked 15 seconds before compressor start up to be sure the 
pressure switch is closed and then ignored for the first 2 minutes 
after the compressor output (BO-2) is enabled. If the switch is open 
continuously for (30) seconds during compressor operation the 
compressor output (BO-2) will be disabled. The compressor will 
not restart until the compressor short cycle time delay has been 
satisfied.

Condensate Overflow

The condensate overflow sensing circuit will monitor the 
condensate level as a resistance input to AI-3. If the condensate 
water level rises resulting in the input resistance rising above the 
set point for the recognition delay period, the condition will be 
recognized as a fault. The condensate will be subjected to a (30) 
second lockout delay which requires that the fault be sensed for a 
continuous (30) seconds before suspending unit operation.

Alarm Output (BO-6)

The alarm output will be enabled when the control is in the lockout 
mode and will be disabled when the lockout is reset.

Test Mode

Raising the zone temperature input (AI-1) reading to 180–220°F 
or by holding the ESC and down arrow keys on the MUI for 5 
seconds will put the control into test mode.  In test mode the 
random start delay and the compressor fixed on delay time will 
both be shortened to 5 seconds and the reversing valve will be 
allowed to cycle with out shutting down the compressor. If an MUI 
is connected to the control LED 8 will flash and the words “Test 
Mode Enabled” will be shown on the LCD display when the control 
is in test mode. Test mode will be disabled after a power cycle, 30 
minute timeout, or by holding the ESC and Up arrow keys on the 
MUI.

Sequence of Operation

Power Fail Restart

When the controller is first powered up, the outputs will be 
disabled for a random start delay.  The delay is provided to 
prevent simultaneous starting of multiple heat pumps.  Once the 
timer expires, the controller will operate normally.

Random Start Delay

This delay will be used after every power failure, as well as 
the first time the compressor is started after the control exits 
the unoccupied mode or the emergency shutdown mode.  The 
delay should not be less than 1 second and not longer than 120 
seconds. If the control is in test mode the random start delay will 
be shortened to 5 seconds.

Controls - FX10 cont.

Summary of Contents for RC Series

Page 1: ...Installation Manual RC Series Geothermal Water Source Heat Pump R 410A Refrigerant 0 75 1 5 Tons Single Speed Installation Information Water Piping Connections Electrical Startup Procedures Troubleshooting Preventative Maintenance ...

Page 2: ......

Page 3: ...ing 17 Open Loop Ground Water Systems 18 Electrical Connections 19 Auxiliary Heat Ratings 19 Electrical Data 20 Fan Performance Table 20 Wiring Schematics 21 25 Controls 26 40 Startup Notes 41 Startup Checklist Unit Startup Steps 42 Operating Parameters 43 Operating Limits 43 Startup Troubleshooting Form 44 Pressure Drop 45 Preventive Maintenance 46 Replacement Procedures 46 ...

Page 4: ...ation only w t stat control option 2 5 FX10 w Open N2 Com Card only w t stat control option 2 6 FX10 w Lonworks Com Card only w t stat control option 2 7 FX10 w BacNet Com Card only w t stat control option 2 Vintage A Current Non standard Option Details SS Standard Option Air Coil Insulation Option 1 FormiShield Extended Range 2 FormiShield Standard Range 3 No Coating Extended Range 4 No Coating S...

Page 5: ...he packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Water Piping The proper water flow must be provided to each unit whenever the unit operates To assure proper flow use pressure temperature ports to determine the flow rate These ports should be located at...

Page 6: ... 3 124 7 29 8 10 9 09 12 15 18 F B G I J C E D A H FILTER BRACKET FILTER BRACKET RIGHT RETURN TOP FRONT LEFT RETURN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN B A REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE...

Page 7: ... 4 124 7 29 8 10 9 09 12 15 18 REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE ON BROKEN EDGE OF LEG AS SHOWN H I J C F E A D G B RIGHT RETURN TOP FRONT LEFT RETURN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN DETAIL A TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN RE...

Page 8: ...0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 FILTER BRACKET FILTER BRACKET A D E C H I J F B G A B RIGHT RETURN TOP FRONT LEFT RETURN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN DETAIL A TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAM...

Page 9: ...DE NORMAL BOILERLESS SWITCH OPTIONAL FAN OPTION SWITCH OPTIONAL BACK PLATE REQUIRED FOR DAMPER INSTALLATION OUTSIDE AIR DAMPER OPTION FIELD INSTALLED LOW VOLTAGE TERMINALS FX10 REMOTE WALL STAT OPTIONS ONLY OPTIONAL FUSED NON FUSED DISCONNECT OPTIONAL BALL VALVES OPTIONAL HOSE KITS CONDENSATE DRAIN CONNECTION FILTER HANDY BOX Dimensional Data Right Return Controls Detail ...

Page 10: ... 65 65 2 19 83 50 4 1 64 4 2 12 03 30 6 0 66 1 7 2 75 7 0 5 5 14 0 DAMPER OPENING Models 09 12 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 42 88 108 9 34 0 86 4 1 5 3 8 1 5 3 8 4 32 11 0 8 88 22 6 FILTER CONTROL PANEL 25 25 64 1 0 86 2 2 11 75 29 8 1 0 2 5 12 0 30 5 4 5 11 4 2 0 5 1 20 6 52 3 19 5 49 5 CONDENSATE DRAIN CONNECTION WATER OUT 1 2 FPT WATER IN 1 2 FPT OPTIONAL BACK PLATE COMPRESSOR AC...

Page 11: ...CONNECTION FILTER HANDY BOX OPTIONAL ELECTRIC HEAT OPTIONAL BACK PLATE REQUIRED FOR DAMPER INSTALLATION OUTSIDE AIR DAMPER OPTION FIELD INSTALLED CONTROL PANEL REMOVE FOR ACCESS TO CONTROL BOX DAMPER ON OFF SWITCH COMPRESSOR ACCESS PANEL REMOVED FOR CLARITY BOTH SIDES ELECTRIC HEAT MODE NORMAL BOILERLESS SWITCH OPTIONAL FAN OPTION SWITCH Dimensional Data Left Return Controls Detail ...

Page 12: ... COMPRESSOR ACCESS PANEL DAMPER OPENING 43 37 110 2 1 62 4 1 25 65 65 1 19 83 50 4 Models 09 12 8 88 22 6 34 0 86 4 1 50 3 8 1 50 3 8 4 32 11 0 42 88 108 9 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL FILTER CONTROL PANEL 1 00 2 5 11 75 26 2 4 5 11 4 0 86 2 2 2 0 5 1 25 25 64 1 20 6 52 3 19 5 49 5 12 0 30 5 CONDENSATE DRAIN CONNECTION WATER OUT 1 2 FPT WATER IN 1 2 FPT 33 0 83 8 13 90 35 3 11 78 29...

Page 13: ...hims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matting may be placed under the chassis to eliminate vibration on hard flooring surfaces Make sure back plate is level Mark and cut floor or wall penetrations for electrical wiring water and condensate piping Optional Electrical Disconnect and Motorized Outside A...

Page 14: ...tion system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The piping material used must comply with all local codes Refer to System Cleaning and Flushing procedures Pipe Locations Figure 2 CONSOLE CABINET CONSOLE CHASSIS CONDENSATE DRAIN LOCATION WATER CONNECTIONS TARGET AREA FOR WALL PENETRATION FUSED ELECTRICAL DISCONNECT O...

Page 15: ...ould be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the supply and return water lines Step 9 Set Unit Controls Locate the continuous fan cycle fan switch within the electrical compartment of the chassis and set to desired position Remote wall thermostat units do ...

Page 16: ...et repositioning pieces 4 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the proper direction when replacing the grille section Replace grille frame assembly into cabinet and secure by replacing 5 mounting brackets Replace cabinet by sliding it down over the top of the chassis 6...

Page 17: ...ct the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure In boiler tower application set the loop control panel set points to desired temperatures Supply power to all...

Page 18: ...iance in your area Note For open loop groundwater systems or systems that do not contain an antifreeze solution set SW1 Switch 2 to the WELL posi tion Refer to the Dip Switch Field Selection table Slow opening closing solenoid valves type VM are recommended to eliminate water hammer Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacter...

Page 19: ...X2 X1 W2 Field Connections Unit Connections 24 VAC COMMON COMPRESSOR REVERSING VALVE FAN LOCKOUT SIGNAL SHUTDOWN NIGHT SETBACK LOAD SHED Requires common connections or 24 VAC for activation Red Black Yellow Orange Green Brown Blue Violet Pink Figure 5 Model Rated Voltage Voltage Min Max Heater Element Watts Fan Motor FLA Heater Element FLA Total Unit FLA Min Circuit Amp Max Fuse Brkr 09 12 208 60 ...

Page 20: ...500 fpm by 0 16 in wg Electrical Data Model Rated Voltage Voltage Min Max Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA 09 208 230 60 1 197 253 6 4 4 1 21 0 0 50 4 6 5 6 10 265 60 1 238 292 na 4 3 22 0 0 50 4 8 5 9 10 12 208 230 60 1 197 253 7 7 4 9 25 0 0 50 5 4 6 7 10 265 60 1 238 292 na 5 3 22 0 0 50 5 8 7 1 10 15 208 230 60 1 197 253 9 2 5 9 29 0 0 69 6 6 8 1 1...

Page 21: ...ite 20 Orange 14 Orange 21 Black 29 Red 30 Black Black 12 White 18 Red 11 Red 19 Red 17 24 V Accessory 24VAC Shutdown Red 15 Red 16 NOTE 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low Pressure Switch RV Reversing Valve Coil ST Entering Air Temperature Sensor RB Blower Relay Black Black Red 11 Black 12 Red 17 Red 19 Black 25 White 28 Black 31 Red 32 Brown 26 RB 4 2 5 Red RV DT ON OFF...

Page 22: ...ack 27 RB 4 2 5 Red EH T2 T1 L2 White White L1 EH Normal RV DT ON OFF Damper Sw Damper Motor D Fan Mode Sw 4 5 2 E1 E1 AQ Blk Wht 24 Blk Wht 23 Black 22 White 18 Blue T6 NOTE 2 3 1 RB 3 1 Black 37 Blue 38 Blue Wht 36 Blue Wht 35 White 34 Blue T6 FS Yellow 44 Yellow 44 Brown 43 Yellow 13 Blue Tan 41 Blue 40 White 28 Blue 40 Brown 3 Tan 41 Brown 26 Green 00 Red 39 Gray 42 NOTE 3 NOTE 4 Violet 4 Viol...

Page 23: ...ON Current fault or Output display mode activated Normal Standard timings Well Open loop freeze sensing setting 30 F Normal Unit status display Normal Standard thermostat operation Normal Standard delay on call from compressor used Refer to LED Display Mode table for position of SW1 4 and SW2 LogicBoard DIP Switch Settings Normal Control Timing Table Blower offdelay Compressor on delay Shortcycle ...

Page 24: ...g information for specific thermostat hookup instructions Red Black 25 RB Gray 42 White 28 Black 29 Red 30 Damper Motor Off On DAMPER MODE DT D Blue Wht 35 MV Black 31 Red 32 Handi Box Ground Lug Unit Power Supply 208 230 60 1or 265 277 60 1 G C R Y1 O G L S Terminal Board X2 X1 W1 Red Bl ack Yellow Orange Brown Green NOTE 2 Violet Pink Bl ue 1 3 4 2 NOTE 1 ES Emergency Shutdown Black White Black ...

Page 25: ...reeze protection Field Zone Sensor Wiring 3 Acc 1 output is cycled with the compressor 4 Acc 2 output is cycled with the fan 5 R C Y1 O and G inputs are for use with a wall mounted thermostat A23 A13 A11 A21 A12 A25 A22 Open Jumper Closed Jumper 2 TB R C Y1 O G L X1 X2 24VAC 24V COM Alarm Acc 1 Acc2 Fan Rev Valve Comp SS AIC RS SC TO Setpoint Shift AI Com Room Sensor Sensor Com Temp Occ EHC T2 T1 ...

Page 26: ...cts Optional Medium User Interface MUI can be used as a field service tool Standalone Unit Mounted Digital Dial Sensor Remote Mounted Standard Thermostat Remote Mounted Sensor FX10 w N2 FX10 Control functions as both unitary heat pump control and DDC communica tion therefore detail operational and fault information is available to BAS Other features are same as FX10 with addition of Johnson Contro...

Page 27: ...is disabled Optional Versatec Microprocessor Control Features The Versatec microprocessor board provides control of the entire unit as well as outputs for status modes faults and diagnostics The control system is a microprocessor based control board that is located in the unit control box This feature is available for either unit mounted controls or optional remote wall mounted thermostat A 9 pin ...

Page 28: ...fault recognition delay 30 seconds Low pressure fault bypass delay 2 minutes Freeze sensing fault bypass delay 2 minutes Power on delay 5 minutes Normal Control Timing Operational Logic Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Miniumum compressor on time 5 seconds except for fault condition High pressure fault recognition delay Less than 1 second low pr...

Page 29: ...er Coil Low Temperature Freeze Sensing Condensate overflow sensing Lockout mode control Emergency shutdown mode Random start and short cycle protection Short Cycle Protection Allows a minimum compressor off time of four minutes and a minimum on time of two minutes Random Start A delay of 1 to 120 seconds is generated after each power up to prevent simultaneous startup of all units within a buildin...

Page 30: ... on from a BAS as needed An alarm history can be viewed through the MUI and will be held in memory until the unit is power cycled Relative humidity can be read by a 0 5VDC humidity sensor that is displayed over the network If you are using an ECM fan motor the control can enable dehumidification mode based on a set point in the control The dehumidification set point itself can also be changed over...

Page 31: ...ow Temp Limit fault High Pressure BI 11 The high pressure switch shall be a normally closed NC switch that monitors the systems refrigerant pressure If the input senses the high pressure switch is open it must disable the compressor output immediately and count the fault The compressor minimum on time does not apply if the high pressure switch opens The compressor will not restart until the compre...

Page 32: ... ECM2 blower will operate in high speed During the heating cycle the reversing valve will be commanded into the off position Cooling Cycle On a call for cooling the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied If the compressor short cycle time delay has been satisfied the compressor will turn on after the blower enable ...

Page 33: ...ng Limit Set Point BI 5 The water coil low temperature freeze sensing limit set point input allows you to adjust the water coil low temperature freeze sensing limit set point AI 5 When the jumper is installed on BI 5 Wire 24 the water coil low temperature freeze sensing limit set point is factory set for 30 F When the jumper on BI 5 Wire 24 is removed the water coil low temperature freeze sensing ...

Page 34: ...Water to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input OFF Occ Input Occ Temp Occ Inp OFF Condensate NML Emg Input Run Lo Press ON Hi Press ON Rndm Tmr 0 BI 4 Input OFF Status Zone Temp 77 2 ºF Dis Air Temp 51 0 ºF Eff Clg Setpt 70 0 F Eff Htg Setpt 66 0 F Water Coil 77 8 F...

Page 35: ...Bad Sensor 0 Alm History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occurred more than 4 times Alarm lock outs are reset by cycling power by pressing the ESC and Return keys simultaneously for a minimum of 15 seconds or by commanding the nviAlarmReset over the BAS network Test...

Page 36: ...ating Freeze Sensing Temperature Value Read Only ADF 40 nvoHtgFrzSetpt Heating Freeze Sensing Temperature Setpoint Value Read Only ADF 41 nvoAlarms Alarms Enumerated 0 no alarms 1 condensate alarm 2 Compressor Hi Discharge Pressure alarm 3 Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only ADF 62 nvoPWMOut ECM PWM Control signal val...

Page 37: ... Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only nvoPWMOut SNVT_volt 44 ECM PWM Control signal value Read Only nvoECMOvrd SNVT_volt 44 ECM PWM Control signal Override Read Write nvoHumidity SNVT_volt 44 Space Humidity value Read Only nviAO2 SNVT_lev_percent 81 Spare PWM Output AO2 Command Write nvoAO2 SNVT_lev_percent 81 Spare PW...

Page 38: ...m 9 Loss of Charge Read Only Analog Input 0 8 Present_Value 85 WFI ECM Cmd Output Present_Value ECM PWM Control signal value Read Only Analog Output 1 2 Present_Value 85 WFI ECM Fan Ovrd Present_Value ECM PWM Control signal Override Read Write Analog Input 0 5 Present_Value 85 WFI Space Humidity Present_Value Space Humidity value Read Only Analog Output 1 3 Present_Value 85 WFI AO2 Override Presen...

Page 39: ...k to send space temperature values to the heat pump controller volatile these will supersede any temperature sensor connected to the space temperature Analog Input Analog Value Type 2 2 1 Occupied Cool Write Cooling setpoint in Occupied mode 2 2 Unoccupied Cool Write Cooling setpoint in Unoccupied mode 2 3 Occupied Heat Write Heating setpoint in Occupied mode 2 4 Unoccupied Heat Write Heating setp...

Page 40: ...and equivalent of a thermostatic G call 14 3 Compressor Cmd Y1 Write allows a network command equivalent of a thermostatic Y1 call 14 4 Compressor Cmd Y2 Write allows a network command equivalent of a thermostatic Y2 call 14 5 Reversing Vlv Cmd O Write allows a network command equivalent of a thermostatic O call 14 6 Emergency Overide Write provide rapid shutdown of the heatpump for fire etc 1 Nor...

Page 41: ... in five models with equip ment rated fuses to provide additional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect CFD 10 10 amp rated fuse CFD 12 12 amp rated fuse CFD 15 15 amp rated fuse CFD 20 20 amp rated fuse CFD 25 25 amp rated fuse Motorized Outside Air Damper A field installed motorized outside air damper is a...

Page 42: ...tpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P T plugs and comparing to unit capacity data in specification catalog 5 Check the temperature of both the supply and discharge water Refer to Unit Operating Para...

Page 43: ...ormance based on entering air temperatures of 80º F DB 67º F WB Heating performance based on entering air temperature of 70º F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Ambient Air 80 26 7 70 21 1 Max Ambient Air 100 37 8 85 29 4 Min Entering Air 50 10 0 40 4 4 Rated Entering Air db wb 80 6 66 2 27 19 68 20 0 Max Entering Air db wb 110 83 43 28 3 80 26 7 Water Limi...

Page 44: ...for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EXPANSION VALVE F AIR COIL F F PSI PSI BRINE IN BRINE OUT COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE F Line Voltage Loop Open Unit Amp Draw Closed DEA...

Page 45: ... 1 2 1 0 0 9 0 8 0 7 0 6 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 12 1 5 0 9 0 8 0 7 0 6 0 5 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 15 2 0 1 7 1 6 1 5 1 4 1 3 3 0 3 3 3 2 3 0 2 9 2 8 4 5 5 7 5 5 5 3 5 1 4 9 18 3 0 1 7 1 6 1 5 1 4 1 3 4 0 4 1 4 0 3 9 3 7 3 6 5 5 7 9 7 6 7 4 7 2 6 9 3 4 08 ...

Page 46: ...re Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly Should periodic coil cleaning be necessary use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines Generally t...

Page 47: ......

Page 48: ...Product RC Series Type Geothermal Water Source Heat Pump Size 0 75 1 5 Tons Document Type Installation Manual Part Number 146 00 NOM4 Release Date 02 10 ...

Reviews: