- the HB outputs have a configurable frequency from 1 Hz to 10 KHz
- All outputs can then be managed as a square wave, with configurable Time ON and Time OFF, from 0.1 to
10 sec
The management parameters of each single output are:
For every output user can set:
•
MAX continuous current
: this is the trip level of cut off current. After Over Current Latch-off
Time the output will be disabled
•
Over Current Latch-off Time
: during this period, we allow current over MAX selected by user
•
Number of Retries
: after latch-off occurred, pdm retries to activate out up to this setting value
•
Retry Delay
: time between retries
•
Minimum current
: this is the low level of current allowed. Lower value activates the alarms for
Open load
•
Check Open Load in Off State
: available for L and M output types. Check load presence also in
OFF state. If you enable this check, a very low current constantly flows through the output, and,
sometimes, it is enough for activating the connected device
•
Soft Start and Soft Stop
are useful to reduce high inrush current. These settings perform a first
stage activation with PWM going from 0 to 100% and viceversa in deactivation. User could also
set a duration time for this mode. In case of PWM mode selected on this out, soft start reaches
user PWM value.
•
In B type outputs, there is also the possibility to set PWM frequency
Summary of Contents for PDM 32
Page 1: ...PDM 32 User Manual VER 1 06 ...
Page 42: ...www aim sportline com PDM 32 User Guide 41 ...
Page 61: ...www aim sportline com PDM 32 User Guide 60 Appendix A Connectors and Pinout ...
Page 62: ...www aim sportline com PDM 32 User Guide 61 ...
Page 63: ...www aim sportline com PDM 32 User Guide 62 Appendix B Mechanical Drawings ...