9.0 Field Terminations
There are several standard and optional outs for transmitted remote information.
Standard
a) Alarm Relay: Normally open form C
Terminal Block #3, #1 and #2.
Optional
The temperature, humidity, and cabinet values can be retransmitted with a 0-10VDC
signal scaled as shown.
a) Pressure: 0-10VDC Conversion: In-H
2
0= (VDC*25)-2500
Terminal Block #3, #3 (pos), #4 (neg)
b) Temperature: 0-10VDC Conversion: Temp °F = (VDC*25)-5
Terminal Block #3, #5(pos), #6 (neg)
b) Humidity: 0-10 VDC Conversion: RH% = (VDC*25)-25
Terminal block #3, #7(pos), #8(neg)