background image

SECTION 5

Existing Construction

1.  Place the collar/damper in the selected location and trace a circle 

onto the surface. From the interior side of the room, cut through the 

surface. Please note: Take care not to damage the ceiling and make a 

smooth cut 

(Figure 6).

2.  Position the collar/damper in the previously cut hole so that it is flush 

with the finished ceiling and secure to the joist/stud using the provided 

1” wood screws through the mounting strap 

(Figure 4).

3.  Install the grill into the collar by pushing it firmly inward towards the 

collar until it fits flush against the wall/ceiling material 

(Figure 5).

SECTION 6

Ducting

CAUTION:

 ALL DUCTING MUST COMPLY WITH LOCAL AND 

NATIONAL BUILDING CODES.

NOTE:

 Insulated ducting is required for bathroom exhaust applications, where 

ducting passes through unconditioned space or where noise is a factor. 

Failure to use insulation could result in excessive condensation buildup within 

the duct, and undesirable sound levels within the room. Duct runs should 

have as few bends as possible.

NOTE: 

Flexible insulated ducting may be used where allowed by local 

code. For the quietest possible installations, it is recommended a minimum 

of 8’ of insulated flexduct be used between any exhaust grill and fan. 

When using flexible type duct work, duct should be stretched as tight and 

straight as possible. Failure to do so could result in dramatic loss of system 

performance. Flexible duct should be connected to the fan with screw clamps 

or duct tape. All connections should be as airtight as possible to maximize 

system performance.

1.  Connect one end of the ducting (not included) to the room level collar/

damper and the other end to the “Y” transition. Secure both ends in place 

using tape or a screw clamp to create as air tight a seal as possible. 

Repeat this step for the other room level grill housing 

(Figure 7).

www.airkinglimited.com

A210952017 Rev. B 8-12

3 of 12

NOTE:

 Units that include only one collar do not utilize the “Y” transition. 

Follow the same instructions as in step 1, except connect the one end of 

the ducting directly to the fan.

2.  Connect one end of the ducting to the top of the “Y” transition and the 

other end to the intake of the fan 

(Figure 7).

3.  Connect one end of the ducting to the exhaust of the fan and the other 

end to a wall or ceiling cap 

(Figure 7).

 Always duct the fan to the 

outside through a wall or roof cap.

NOTE:

 When using insulated flex duct, it is recommended that the inner vinyl 

core be screw clamped or taped to the inlet and outlet and that the vapor 

barrier surrounding the insulation be taped to the fan housing.

NOTE:

 When attaching flex duct to the collar/damper combination and an 

immediate elbow is necessary, be certain that the elbow is installed with a 

“soft” bend to allow damper blades to operate properly.

SECTION 7

Installing Optional Balancing Damper

Some kits include an optional balancing damper to allow for adjustment of 

the system. The damper may be used where the grills will be connected 

using branches of unequal length or where the flow will need to be balanced 

for any reason. To Install the optional damper:
1.  The damper must be installed on the branch with the least restriction. 

This is generally the duct that is shortest or has the fewest bends.

2.  Drill a 5/16” hole approximately 1-1/2” from the edge on the flat side 

of the “Y” transition.

3.  Insert the shaft of the damper into the hole drilled in step 2. Place the 

washer, handle, then wing nut onto the shaft

 (Figure 8).

Figure 5

Collar/Damper

Grill

Figure 6

Exhaust to 

Wall/Roof Cap

Figure 7

Fan

“Y” Transition

Ducting

Collar/Damper

Wing Nut

Washer

Hole

Handle

Shaft

Damper

“Y” Transition

Figure 8

Summary of Contents for AIF10X

Page 1: ...ll applicable codes and standards including fire related construction b Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to pre...

Page 2: ...ber vibration isolation grommets to prevent the transmission of sound through the structure Be careful not to over tighten Also care should be taken not to strip the plastic housing Screws are self ta...

Page 3: ...e or a screw clamp to create as air tight a seal as possible Repeat this step for the other room level grill housing Figure 7 www airkinglimited com A210952017 Rev B 8 12 3 of 12 NOTE Units that inclu...

Page 4: ...IAR WITH METHODS OF INSTALLING ELECTRICAL WIRING SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN 1 Remove the screws securing the terminal box cover plate located on the side of the motor Figure 9 2 Ru...

Page 5: ...E PRODUCT WHICHEVER FIRST OCCURS AND IN NO EVENT SHALL AIR KING S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY INCLUDE I INCIDENTAL OR CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER OR II REPLACME...

Page 6: ...7 1 Y Transition AIK24Y 5S7635008 1 Y Transition AIK26Y 5S7635010 8 12 Screw 5S7699022 9 2 Collar Damper Assembly AIK24Y 5S7635039 2 Collar Damper Assembly AIK26Y 5S7635015 10 2 Grill AIK24Y 5S763501...

Page 7: ...t la construction relative aux incendies b De l air en quantit suffisante est requis pour la bonne combustion et l vacuation de gaz par le conduit chemin e provenant d quipement de br lage au combusti...

Page 8: ...ge soit facilement accessible Figure 2 www airkinglimited com A210952017 Rev B 8 12 8 of 12 REMARQUE Le support est muni de passe c bles isol s en caoutchouc pour la vibration afin d emp cher la trans...

Page 9: ...pi ce et l autre extr mit l embranchement en Y Fixez les deux extr mit s en place en utilisant du ruban ou un serre joint afin de cr er un joint aussi tanche que possible R p tez cette tape pour le c...

Page 10: ...DES D INSTALLATION DE C BLAGE LECTRIQUE RECOURREZ AUX SERVICES D UN LECTRICIEN QUALIFI 1 Retirez les vis de la plaque du couvercle de la bo te de raccordement situ e sur le c t du moteur Figure 9 2 Pa...

Page 11: ...IER ET DANS AUCUN CAS AIR KING N ASSUME AUCUNE RESPONSABILIT EXPRESSE OU TACITE POUR I DES DOMMAGES ACCIDENTELS OU INDIRECTS DE N IMPORTE QUELLE CAUSE OU II LE REPLACEMENT OU LA R PARATION DE TOUS FUS...

Page 12: ...Y AIK26Y 5S7635010 8 12 Vis 5S7699022 9 1 Assemblage collet clapet AIK24Y 5S7635039 1 Assemblage collet clapet AIK26Y 5S7635015 10 1 Grille AIK24Y 5S7635016 1 Grille AIK26Y 5S7635017 11 8 Ressorts pou...

Reviews: