background image

2b. 

TWO SPEED UNITS

 (models ES80DG and ES130DG): Plug the fan’s 2 

pin and 3 pin quick connect motor cords into the receptacles located 
on the side of the wire compartment. Plug the 3 pin quick connect 
cord from the motion sensor on the grill into the receptacle coming out 
of the top of the wire compartment. These cords will only fit one way 
into the receptacles 

(Figure 12).

3.  Install the ceiling mounting flange to cover any gaps which exist 

between the housing and the finished ceiling. Remove the two screws 
that connect the ceiling mounting flange to the housing. Put caulk (not 
provided) on each corner of the ceiling mounting flange to ensure that 
the flange fits tightly against the ceiling. Line up the screw holes in the 
ceiling mounting flange with the screw holes on the inside of the housing 
and press flange in place so it is tight against the ceiling. Reinstall ceiling 
flange mounting screws inside the housing 

(Figure 13)

.

NOTE:

 If the housing is mounted to far or not far enough into the ceiling for 

the flange to make a solid connection, loosen the mounting channel and 
adjust the housing up or down on the rails. Once in place, fully tighten the 
mounting channel nuts.

4.  Install the grill by squeezing the spring furthest from the motion 

sensor together and installing it up into the slot furthest from the wire 
compartment on the fan’s housing. Attach the 3 pin quick connect 
from the motion sensor on the grill to either the harness installed in 

Step 2a 

(Single Speed Models) or the connector from the top of the 

wire compartment (Two Speed Models). This cord will only fit one way 
into the receptacle. Install the other spring in place and push the grill 
up into position 

(Figure 14).

www.airkinglimited.com

A210572215 Rev. D 8-12

4 of 12

5.  Restore power and test your installation.

SECTION 7

Programming the Occupancy Sensor

1a. 

Setting the Occupancy Time Delay.

 This will set 

the amount of time the fan will continue to operate 

after the room is vacated or on dual speed models 

the amount of time the fan will run on high speed. 

Locate the motion sensor on the fan’s grill and 

press the button 2 times. The LED on the sensor 

will then flash the number of times to indicate the 

current setting, this will repeat 3 times:

 

 

1 time = 30 seconds 

 

 

2 times = 2.5 minutes 

6 times = 12.5 minutes

 

 

3 times = 5 minutes  

7 times = 15 minutes 

 

 

4 times = 7.5 minutes  

8 times = 17.5 minutes

 

 

5 times = 10 minutes  

9 times = 20 minutes

1b. To adjust the setting, while the sensor is still flashing from 

Step 1a

press the button the number of times that corresponds with the 

amount of time you desire, for instance 3 times sets the delay to 

5 minutes (see numbers in 

Step 1

). The sensor will then flash the 

number of times for the new setting 3 times before exiting back to the 

programming mode.

2a 

Setting the Minimum On Time.

 This sets the minimum time the fan 

will operate once motion is detected within the room or on dual speed 

models the amount of time the fan will run on high speed. This works 

in conjunction with the Occupancy Time Delay feature set in 

Steps 1a

 

and 

1b

. For instance if you set the minimum time on for 15 minutes 

and the Time Delay for 5 minutes, the fan will operate for at least 15 

minutes then 5 additional minutes.

 

NOTE:

 This is a minimum time that the fan will operate. If the room is 

occupied longer, the fan will continue to run until the room is vacated 

and the occupancy time delay has elapsed.

2b. Locate the motion sensor on the fan’s grill and press the button 10 

times. The LED on the sensor will then flash the number of times to 

indicate the current setting, this will repeat 3 times:

 

 

1 time = 0 minutes  

4 times = 45 minutes

 

 

2 times = 15 minutes 

5 times = 60 minutes

 

 

3 times = 30 minutes

2c.  To adjust the setting, while the sensor is still flashing from 

Step 2b

press the button the number of times that corresponds with the 

amount of time you desire, for instance 3 times sets the minimum on 

time to 30 minutes (see numbers in 

Step 2b

). The sensor will then flash 

the number of times for the new setting 3 times before exiting back to 

the programming mode.

3.  Once all setting have been made and the sensor will return to detection 

mode and the LED will flash when occupancy of the room is detected.

Figure 12

Figure 13

Screws

Ceiling 

Mounting 

Flange

Screw Holes

Figure 14

Figure 11

From 

Motor

From 

Sensor

From 

Motor

From Motor

From 

Sensor

From Motor

Summary of Contents for ES130DG

Page 1: ...t be done by qualified person s in accordance with all applicable codes and standards including fire related construction b Sufficient air is needed for proper combustion and exhausting of gases throu...

Page 2: ...ing material Figure 3 Set housing aside and cut opening being careful not to cut or damage any electrical or other hidden utilities Install the rails into the mounting channel on the housing Center th...

Page 3: ...com A210572215 Rev D 8 12 3 of 12 3b Intermittent Ventilation For two speed fans wired for intermittent ventilation with a standard duplex toggle switch such as Leviton 5224 2W not included Connect t...

Page 4: ...fan s grill and press the button 2 times The LED on the sensor will then flash the number of times to indicate the current setting this will repeat 3 times 1 time 30 seconds 2 times 2 5 minutes 6 tim...

Page 5: ...LL WARRANTIES EXPRESSED OR IMPLIED INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY LAST ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE OR UNTIL THE ORIGINAL PURCHASER OF THE PRODUCT...

Page 6: ...REPLACEMENT PARTS DIAGRAM Qty Description Replacement Part 14 1 18 ga Ground Wire 5S1999111 15 1 Wire Compartment Assembly ES80SG 5S1239016 1 Wire Compartment Assembly ES130SG 5S1239017 16 1 Wire Com...

Page 7: ...en conformit avec tous les codes et normes applicables incluant la construction relative aux incendies b De l air en quantit suffisante est requis pour la bonne combustion et l vacuation de gaz par l...

Page 8: ...ention de ne pas couper ou endommager les installations lectriques ou d autres utilit s masqu es Installez les rails dans le canal de montage sur le bo tier Centrez le canal de montage dans les fentes...

Page 9: ...ses c bl s pour la ventilation intermittente avec un interrupteur bascule duplex standard tel que Leviton 5224 2W non inclus Reliez le fil blanc du ventilateur au fil neutre blanc de la source d alime...

Page 10: ...gril du ventilateur et appuyez sur le bouton 2 fois Le LED sur le capteur clignotera alors le nombre de fois pour indiquer le r glage actuel Ceci sera r p t 3 fois 1 fois 30 secondes 2 fois 2 5 minut...

Page 11: ...ntie Air King son choix r parera ou remplacera n importe quelle partie ou pi ces qui s av rent d fectueuses ou remplacera le produit entier par le m me mod le ou un mod le comparable CE QUE CETTE GARA...

Page 12: ...RAMME DES PI CES DE REMPLACEMENT de pi ce Qt Description de remplacement 14 1 Fil de mise la terre de calibre 18 5S1999111 15 1 Assembl e du compartiment du fil ES80SG 5S1239016 1 Assembl e du compart...

Reviews: