background image

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

SECTION 1

Preparing the Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the 

fan you should have:

 

 

2 - Collar Assembly (attached) 

 

 

2 - Mounting Brackets (attached)

 

 

1 - Controller (attached)

 

 

1 - Instruction/Safety Sheet   

2. 

Choose the location for your fan. To ensure the best air and sound performance, it 

is recommended that the length of ducting and the number of elbows be kept to a 

minimum, the radius of each elbow be as large as possible for the installation, and that 

insulated hard ducting be used. This fan will require at least 12" of clearance in the 

ceiling or wall. The fan mounts using the provided mounting brackets or can be surface 

mounted to a wall or ceiling.

NOTE:

 The fan must be installed into a location that can be easily accessed once installed.

3. 

No additional vibration deadening materials are needed for this fan.

SECTION 2

Mounting the Fan

1. 

Confirm the fan is positioned so the air flow is in the correct direction.

2a. 

Surface Mounting: 

Locate at least one stud or joist. Place the fan in position so that the 

mounting bracket is centered on the stud or joist and make the location for the four (4) 

holes. Remove the fan and install properly rated wall/ceiling anchors for the holes that 

do not go directly into a joist or stud. Position fan in place and secure with screws (not 

included) 

(Figure 1).

2b. 

Mounting to a Joist:

 Install two - 2 x 4 headers (not included) between the joists. 

Position the fan housing on top of the headers and secure the mounting brackets with 

screws (not included) to the header 

(Figure 2)

.

2c. 

Hanging Bar Mounting: 

Lift unit up onto the threaded rods and secure in place using 

appropriate hardware (not included) 

(Figure 3).

www.airkinglimited.com

6728076 Rev. G 5-17

2 of 8

SECTION 3

Ducting

NOTE: 6" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND 

NATIONAL BUILDING CODES.

NOTE:

 The ducting from this fan to the outside of the building has a strong effect on the air 

flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible 

for best performance, and avoid installing the fan with smaller ducts than recommended. 

Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed 

with existing ducts may not achieve their rated air flow.

WARNING:

 

MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES 

WITH ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET 

AWAY FROM SOURCES OF CONTAMINATION SUCH AS BUT NOT LIMITED TO: DRYER, 

FURNACE OR CENTRAL VACUUM EXHAUSTS, GAS APPLIANCES SUCH AS BBQ GRILLS, 

GARBAGE BINS OR OTHER EXHAUST PORTS.

NOTE: 

To ensure quiet operation of in-line and remote fans, each fan shall be installed using 

sound attenuation techniques appropriate for the installation. For bathroom and general 

ventilation applications, at least 8 feet of insulated flexible duct shall be installed between the 

exhaust or supply grille(s) and the fan. 
1. 

Connect the ducting to the fan’s duct collar 

(Figure 4).

 Seal ducting to housing with 

appropriately rated tape. Use screws or suitable clamps to secure in place. Make sure 

the fresh air intake is connected to a properly installed intake port that is a suitable 

weather hood with insect screen to protect air intake. It is recommended that low 

restriction termination fittings be used.

2. 

Ensure duct joints and exterior penetrations are sealed with caulk or other similar material 

to create an air-tight path to minimize building heat loss or gain and to reduce the potential 

for condensation. Place/wrap insulation around duct and/or fan in order to minimize 

possible condensation buildup within the duct, as well as building heat loss or gain.

NOTE:

 At the base of the duct adapter, there is a small diameter test port hole covered with 

a plastic cap. Make sure the test port is not covered up with the ducting so that it can be 

accessed for pitot tube testing. To access the port, remove the port cover and insert tube.

SECTION 4

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

CAUTION:

 ALL ELECTRICAL CONNECTIONS MUST BE 

MADE IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR 

NATIONAL ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING 

ELECTRICAL WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.

NOTE:

 This unit includes a side access panel for wiring that does not require the removal of the 

fan’s blower assembly.
1. 

Remove the wire compartment cover screw and place cover in a secure place 

(Figure 5).

Bracket

Figure 3

Housing

Threaded Rod

Figure 1

Screws

Stud/Joist

Anchor

Air Flo

w

Figure 5

Screw

Wire 

Compartment 

Cover

Ground 

Screw

Joist

2 x 4 Header

Figure 2

Bracket

12"

Figure 4

Air Flow

Intake  Ducting

Outlet  Ducting

Test Port

Summary of Contents for QuFresh QFAM

Page 1: ...tion b Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the l...

Page 2: ...nergy loss and inhibit mold growth Fans installed with existing ducts may not achieve their rated air flow WARNING MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES WITH ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET AWAY FROM SOURCES OF CONTAMINATION SUCH AS BUT NOT LIMITED TO DRYER FURNACE OR CENTRAL VACUUM EXHAUSTS GAS APPLIANCES SUCH AS BBQ GRILLS GARBAGE BINS OR OTHER EXHAUST PORTS NO...

Page 3: ...s from entering into the living space 1 If you have not already pressed the ON button in step one of this section do so now Press the CONFIGURE button once and the display will show a C and Temp Unit on the right hand side 2 Press the up or down button to display the temperature in Fahrenheit or Celsius 3 Press the CONFIGURE button again to set the upper limit temperature This is the temperature t...

Page 4: ... replaced at least once every 3 months Reverse the instructions in the SECTION 7 of these instructions to remove filter NOTE If you notice a large amount of insects and debris in the air filter this could be a sign that the intake weather hood roof cap or wall cap might be compromised and need repair or replacing CALIFORNIA RESIDENTS ONLY WARNING THIS PRODUCT CAN EXPOSE YOU TO A CHEMICAL OR CHEMIC...

Page 5: ... is not connected properly 1c Turn off power to unit Check that all wires are connected 1d Motor has stopped operating 1d Replace motor 2 Fan is operating but air moves slower than normal 2a Obstruction in the ducting 2a Check for any obstructions in the ducting The most common are bird nests in the roof cap or wall cap where the fan intakes from the outside 2b Filter is clogged 2b Change air filt...

Page 6: ... KING S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY INCLUDE I INCIDENTAL OR CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER OR II REPLACMENT OR REPAIR OF ANY HOUSE FUSES CIRCUIT BREAKERS OR RECEPTACLES NOTWITHSTANDING ANYTHING TO THE CONTRARY IN NO EVENT SHALL AIR KING S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY EXCEED THE PURCHASE PRICE OF THE PRODUCT AND ANY SUCH LIABILITY SHALL TERMIN...

Page 7: ... 5S1650001 2 1 6 Metal Collar Intake 5S1650002 3 1 6 Metal Collar Outlet 5S1650003 4 1 Blower Assembly 5S2202013 5 1 Wire Compartment Assembly 5S1650100 6 3 Adjustment Knobs 5S1299802 7 1 LCD Controller 5S1650004 9 0 8 0 7 0 L o w e r 6 0 5 0 4 0 3 0 High Low 1 3 0 1 2 0 1 1 0 1 0 0 5 6 7 REPLACEMENT PARTS DIAGRAM ...

Page 8: ...www airkinglimited com 6728076 Rev G 5 17 8 of 8 NOTES ...

Reviews: