background image

2. 

Pull the loose black, white and green wires out from the wire compartment (additional 

wires will be present). Install an approved electrical connector to the wire compartment 

cover (not included). Run a black (hot), white (neutral), and a green or bare ground wire 

from the supply through the electrical connector. Connect all wires from the supply 

to their corresponding wires within the wire compartment 

(Figure 6)

. Use approved 

methods for all connections.

3. 

Carefully tuck wires back inside wire compartment and replace wire compartment cover 

securing with the screw that was removed earlier.

SECTION 5

Setting the Speed

1. 

Determine the CFM required. The unit 

can be set from 40 CFM to 120 CFM 

in increments of 10 CFM. Remove the 

screw securing the access panel cover in 

place and open the cover to gain access. 

Locate the speed control panel inside the 

unit 

(Figure 9).

2. 

For setting of 40 CFM to 60 CFM:

 Place 

the rocker switch in the “Low” position 

and the first dial in the “Lower” position 

then set the second dial to the required 

CFM 

(Figure 10).

3. 

For settings of 70 CFM to 90 CFM:

 

Place the rocker switch in the “Low” 

position and set the first dial to the 

required CFM 

(Figure 10).

4. 

For settings of 100 CFM to 120 CFM:

 

Place the rocker switch in the “High” 

position and set the top dial to the 

required CFM 

(Figure 10).

SECTION 6

Optional Air Filter

An air filter (available separately) can be added 

to this unit to provide additional filtration of the 

intake air. The unit will accept a 10” x 10” x 2” 

filter. To install:

NOTE:

 Adding an air filter will decrease the 

airflow of the unit. You will need to increase 

the CFM selected in 

SECTION 6

 to account for 

the decreased air flow. Filters must be changed regularly. Refer to the filter manufacturer’s 

recommendations to determine how often the filter should be changed.
1. 

Remove the screw securing the access panel cover in place and open the cover to gain 

access to the controls and filter area.

2. 

Ensure the filter is facing the correct way and slide the filter into the slot in the housing. 

Make sure the filter is seated all the way to the bottom of the housing 

(Figure 11).

3. 

Close the access panel and reinstall the screw holding the access panel in place.

www.airkinglimited.com

6728076 Rev. G 5-17

3 of 8

SECTION 7

Completing the Installation

NOTE:

 When fan is mounted inline and no penetration is made into unconditioned spaces, there 

is no need to use a sealant appropriate for contact with the building materials present and for 
the temperature requirements of the installation to prevent air leakage from unconditioned 
spaces. Additional material (backing rod, ceiling material) are also not required.
1. 

Close the access panel and reinstall the screw holding the access panel in place.

2. 

Restore power and test your installation.

SECTION 8

Setting the Controller

The unit mounted controller monitors temperature and humidity of incoming air and allows the 

installer to configure optimal ventilation.

With power to the unit turned on, the initial screen will show “OFF”. Press the “ON” button to 

show the current temperature and humidity condition. By pressing the “ON” button, the unit 

will turn on for continuous air flow using the CFM settings from 

SECTION 6

 

Setting the Speed

.

ENERGY SAVING MODE

NOTE: 

This unit is equipped with an Energy Saving Mode that allows you to configure upper 

and lower limits for temperature and humidity. By setting these limits, you will help prevent 

extreme temperature or humidity changes from entering into the living space. 
1. 

If you have not already pressed the “ON” button in step one of this section, do so now. 

Press the “CONFIGURE” button once and the display will show a “C” and “Temp Unit” on 

the right hand side.

2. 

Press the up or down button to display the temperature in Fahrenheit or Celsius.

3. 

Press the “CONFIGURE” button again to set the upper limit temperature. This is the 

temperature that when the outside air coming into the home exceeds, the fan will stop 

and enter sampling mode. You will see “Upper Limit” and “Temperature” on the right 

hand side. Use the “UP” and “DOWN” buttons to adjust the temperature.

4. 

Press the “CONFIGURE” button again to set the upper limit humidity level. This is the 

humidity level that when the outside air coming into the home exceeds, the fan will stop 

and enter sampling mode. You will see “Upper Limit” and “Humidity” on the right hand 

side. Use the “UP” and “DOWN” buttons to adjust the temperature. 

5. 

Press the “CONFIGURE” button again to set the lower temperature level. This is the 

temperature that when the outside air coming into the home falls below, the fan will 

stop and enter sampling mode. You will see “Lower Limit” and “Temperature” on the 

right hand side. Use the “UP” and “DOWN” buttons to adjust the temperature.

6. 

Press the “CONFIGURE” button again to set the lower limit humidity level. This is the humidity 

level that when the outside air coming into the home falls below, the fan will stop and enter 

sampling mode. You will see “Lower Limit” and “Humidity” on the right hand side. Use the 

“UP” and “DOWN” buttons to adjust the temperature. Setting this to 0 or “LO” will override 

the humidity set level. This may be necessary in very low humidity areas of the country. 

7. 

Press the “CONFIGURE” button until it returns to the main screen. You will see “ON” in 

the top left corner of the display. At this point, the information has been stored.

SECTION 9

Using the Controller

1. 

Energy Savings Mode:

 To enter the Energy Savings mode, press the “ON/OFF/ENERGY 

SAVINGS” Button until “Energy Savings” appears on the left side of the display. Energy 

Savings mode engages the settings configured in 

SECTION 8

 

Energy Saving Mode

.

2. 

When the unit is on, the display will show the current conditions (temperature and 

humidity level) as well as if it is in Energy Savings mode or not. Other icons/information 

that may be on the display include:

 

Fan icon appears when the fan is on.

 “HI°

F

” appears if the intake temperature is above 150°F.

 “Lo°

F

” appears if the intake temperature is below 15°F.

 

“Lo%” appears if the intake humidity is below 10%.

3. 

Optional Heater Unit:

 An optional heater unit is available for climates that the air coming 

into the unit falls below 54°F. To install the unit, follow the direction that are included 

with that unit. The display will show a thermometer icon with either a “1” or “1 2” when 

the temperature range is at a level where the heating element would come on if present. 

Stage 1 - “1” turns on when the intake air temperature is between 39°F and 54°F. Stage 

1 and 2 “1 2” turn on when the intake air temperature is between 33°F and 39°F.

4. 

To restore the factory setting, make sure the unit is in the “OFF” setting. Hold both the 

“UP” and “DOWN” buttons for approximately 5 seconds. The “OFF” on the display will 

flash to confirm the settings have been restored.

Figure 6

Supply from house

Black

Neutral (White)

Ground (Green or Bare)

Fa

n

Neutral (White)

Green

Black

Green

ON / OFF / 

ENERGY SAVING

CONFIGURE

UP

DOWN

Figure 10

Rocker Switch

90

80

70

Low

er

60

50

40

High

Low

12

0

11

0

100

Top Dial

First Dial

Second Dial

Figure 11

90

80

70

Low

er

60

50

40

30

High

Low

130

12

0

11

0

100

Filter

Screw

Air Flow

Screw

Figure 9

Summary of Contents for QuFresh QFAM

Page 1: ...tion b Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the l...

Page 2: ...nergy loss and inhibit mold growth Fans installed with existing ducts may not achieve their rated air flow WARNING MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES WITH ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET AWAY FROM SOURCES OF CONTAMINATION SUCH AS BUT NOT LIMITED TO DRYER FURNACE OR CENTRAL VACUUM EXHAUSTS GAS APPLIANCES SUCH AS BBQ GRILLS GARBAGE BINS OR OTHER EXHAUST PORTS NO...

Page 3: ...s from entering into the living space 1 If you have not already pressed the ON button in step one of this section do so now Press the CONFIGURE button once and the display will show a C and Temp Unit on the right hand side 2 Press the up or down button to display the temperature in Fahrenheit or Celsius 3 Press the CONFIGURE button again to set the upper limit temperature This is the temperature t...

Page 4: ... replaced at least once every 3 months Reverse the instructions in the SECTION 7 of these instructions to remove filter NOTE If you notice a large amount of insects and debris in the air filter this could be a sign that the intake weather hood roof cap or wall cap might be compromised and need repair or replacing CALIFORNIA RESIDENTS ONLY WARNING THIS PRODUCT CAN EXPOSE YOU TO A CHEMICAL OR CHEMIC...

Page 5: ... is not connected properly 1c Turn off power to unit Check that all wires are connected 1d Motor has stopped operating 1d Replace motor 2 Fan is operating but air moves slower than normal 2a Obstruction in the ducting 2a Check for any obstructions in the ducting The most common are bird nests in the roof cap or wall cap where the fan intakes from the outside 2b Filter is clogged 2b Change air filt...

Page 6: ... KING S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY INCLUDE I INCIDENTAL OR CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER OR II REPLACMENT OR REPAIR OF ANY HOUSE FUSES CIRCUIT BREAKERS OR RECEPTACLES NOTWITHSTANDING ANYTHING TO THE CONTRARY IN NO EVENT SHALL AIR KING S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY EXCEED THE PURCHASE PRICE OF THE PRODUCT AND ANY SUCH LIABILITY SHALL TERMIN...

Page 7: ... 5S1650001 2 1 6 Metal Collar Intake 5S1650002 3 1 6 Metal Collar Outlet 5S1650003 4 1 Blower Assembly 5S2202013 5 1 Wire Compartment Assembly 5S1650100 6 3 Adjustment Knobs 5S1299802 7 1 LCD Controller 5S1650004 9 0 8 0 7 0 L o w e r 6 0 5 0 4 0 3 0 High Low 1 3 0 1 2 0 1 1 0 1 0 0 5 6 7 REPLACEMENT PARTS DIAGRAM ...

Page 8: ...www airkinglimited com 6728076 Rev G 5 17 8 of 8 NOTES ...

Reviews: