15
Operation
Inlet Temp.
Inlet temperature in°C.
Outside Temp. Vent.
Outside temperature air
handling unit in °C.
Room Temperature
Extraction temperature in°C.
Exhaust Temp. Vent.
Exhaust temperature air
handling unit in °C
Requested Temp.
Setpoint Inlet temperature
in°C.
Max Room Temp.
Setpoint “High room tem-
perature” in °C.
Pre Heater
Connected in %.
Comfort Heate
r
Connected in %.
Inlet Damper
Status On/Off.
Ext. Emerg. Stop
Emergency stop function
status On/Off.
Bypass Damper
Status On/Off.
Bypass Damper
Bypass position in %. (0 =
closed; 100 = fully open)
Supply Fan
Signal voltage supply fan in
Volts.
Extraction Fan
Signal voltage extraction fan
in Volts.
Cooling Module
Operation in %.
Outside Temp.
Outside temperature cooling
module
in °C.
Vaporiser temp.
Vaporiser temperature cool-
ing module in °C.
Condenser temp.
Condenser temperature
cooling module in °C.
Setpoint Cool. Mod.
Cooling module temperature
setpoint in °C.
AI#1
0-10V analogue input 1 in
Volts.
AI#2
0-10V analogue input 2 in
Volts.
AI#3
0-10V analogue input 3 in
Volts.
(Text “AI” at inlet #1 - #3 adapted by programming the
control system.)
Rel. humidity (outside)
Relative humidity (outside
air) in %
Rela. humidity (inside)
Relative humidity (exhaust
air) in %
Operation
Started By
Operation start signal
- “External”, using external contacts
and relays.
- “Airlinq”, manual start using a
control panel.
- “CO2”, using a CO2 sensor.
- “PIR”, using a passive infrared
sensor.
- “BMS”, using an analogue or digital
BMS system.
- “Timer”, using a timer.
- “Holiday mode”, via control panel or
a digital BMS system.
- “Dependent”, on several start
signals.
Operation State
Operation status
- “Automatic”, fully automatic opera-
tion according to programming.
- “Manual”, when the automatically
set air flow or inlet temperature
is changed by the user or a CTS
system.
- “Night time cooling” is activated.
- “Holiday mode” is activated.
- “OFF”, the unit is switched off, and
must be started using the control
panel.
- “Standby”, the unit is temporarily
stopped and will start automatically
according to programming.
System Condition
Active internal control system
function
- “Low temperature”.
- “High temperature”.
See “Internal control system functions” on page 25.
NB: If an option is not installed, no operation value
will show in the status menu.